Precisionaire PB1003 Air Cleaner User Manual


 
Operating
Nominal Size
500 fpm
Media Weight
Efficiency Limit ºF
H x W x D (inch)
Rating
Area Each
cfm pd (sq. ft.) (lbs)
750
24 x 24 x 12 2000
.45
140 26
60-65%
24 x 12 x 12 1000 69 21
900
24 x 24 x 12 2000
.50
175 28
24 x 12 x 12 1000 90 22
750
24 x 24 x 12 2000
.55
140 26
80-85%
24 x 12 x 12 1000 69 21
900
24 x 24 x 12 2000
.60
175 28
24 x 12 x 12 1000 90 22
750
24 x 24 x 12 2000
.65
140 26
90-95%
24 x 12 x 12 1000 69 21
900
24 x 24 x 12 2000
.70
175 28
24 x 12 x 12 1000 90 22
Notes:
1. PD represents clean pressure drop in inches w.g. The recommended final pressure drop is 2.5 inch w.g.
2. Operation down to zero velocity is satisfactory for all models.
3. Efficiencies are average and are based on ASHRAE Standard 52.1 and 52.2 dust spot test methods.
Performance values stated may be averages typical of the products listed. Contact factory for actual perform-
ance test reports on specific products.
4. Perfmormance values shown in this publication may be averages or estimates intended to generally represent
product styles. Always contact factory for latest actual test data on specific Flanders Precisionaire models.
1.0 General
1.1 High temperature rigid filters shall be
PrecisionCell HT separator type as manufactured
by Flanders.
1.2 Filter sizes and temperature ranges shall be as
scheduled on the drawings.
2.0 Filter Construction
2.1 Filters shall be constructed by pleating a contin-
uous sheet of wet-laid micro-fine glass media
into closely spaced pleats with hemmed-edge
corrugated aluminum separators.
2.2 The filter pack shall be sealed into a 24 ga.
aluminized steel frame with fire-retardant
sealant.
2.3 Expanded metal aluminized steel faceguards
shall be installed on the air entering and air leav-
ing sides.
2.4 A 1/2” “T” strap shall be installed on the down-
stream side and 1/2” horizontal strap on the air
entering side.
3.0 Performance
3.1 Initial and final resistance shall not exceed the
scheduled values.
3.2 Media area shall equal that of the scheduled
high temperature filter.
3.3 The manufacturer shall guarantee performance
as outlined in section 7.4 of ARI Standard 800.
Guide Specifications
REPRESENTED BY:
Flanders - PrecisionAire
Foremost in Air Filtration
Toll Free: 1-800-637-2803