Height Filters/ Width Code
Code Weight
1W 2W 3W 4W 5W 6W 7W 8W
1H Filters 1 2 3 4 5 6 7 8
Weight 105 190 270 380 460 540
2H Filters 2 4 6 8 10 12 14 16
Weight 200 305 460 610 765 920
3H Filters 3 6 9 12 15 18 21 24
Weight 255 405 590 810 995 1180
4H Filters 4 8 12 16 20 24 28 32
Weight 345 520 710 1040 1230 1420
Filter Usage and Housing Weight
Model Number Development
(1) Filters/Weight: Top number indicates the number of filters required to fill the unit. Bottom number indicates the
approximate weight in pounds of the housing EMPTY. Add 32 pounds for each HEPA/ULPA filter and 2 pounds per each
prefilter to determine approximate weight when loaded with filters.
Add 10% to calculate the approximate rigging weight of housings
C3G - 1H1W - GGF - GLV - D1
Filter type:
C3G - Gasket Seal
C4F - Fluid Seal
Housing Size:
Filters High x Wide
(See Chart)
Filter Size:
CCF - 12”x12”x11-1/2” HEPA Filter
2CCF -12”x12”x11-1/2” HEPA filter with a 2” prefilter
4CCF -12”x12”x11-1/2” HEPA filter with a 4” prefiler
CGF - 12”x24”x11-1/2” HEPA Filter
2CGF- 12”x24”x11-1/2” HEPA Filter with 2” prefilter
4CGF- 12”x24”x11-1/2” HEPA filter with a 4” prefilter
GCF- 24”x12”x11-1/2” HEPA filter
2GCF- 24”x12”x11-1/2” HEPA filter with 2” prefilter
4GCF- 24”x12”x11-1/2” HEPA filter with 4” prefilter
GGF- 24”x24”x11-1/2” HEPA filter
2GGF- 24”x24”x11-1/2” HEPA filter with 2” prefilter
4GGF- 24”x24”x11-1/2” HEPA filter with 4” prefilter
CC12- 12”x12”x11-1/2” carbon adsorber
CG12- 12”x24”x11-1/2” carbon adsorber
GC12- 24”x12”x11-1/2” carbon adsorber
GG12- 24”x24”x11-1/2” carbon adsorber
CG16- 12”x24”x16” carbon adsorber
GC16- 24”x12”x16” carbon adsorber
GG16- 24”x24”x16” carbon adsorber
GG18- 24”x24”x18” carbon adsorber.
Flanders Filters - Foremost in Air Filtration
Toll Free: 1-800-637-2803
Housing Material:
GLV: Galvanized steel
304: Type 304 S/S
304L: Type 304 L S/S
316: Type 316 S/S
316L: Type 316L S/S
ALZ - 14 gauge aluminized
(non-standard)
The filter size arrangements listed at left are the only standard
arrangements. 6” prefilters are available but non-standard.
Any prefilter with a carbon housing is available but not standard.
Multi-wide CC, CG and GC units are available but non-standard.
CC16, CC18, CG18 & GC18 units are not available.
Door Locations
D1- Filter access and housing on
one side only
D1A - Doors on both sides, but filter
access from one side only.
D2 - Doors on both sides and filter