DRAIN PIPING WORK
CAUTION
Install the drain pipe in accordance with the Installation Manual so that the water is drained completely, and
insulate the pipes so that no condensation forms them.
Improper pipe installation could result in water leaking indoors on furniture, etc.
REQUIREMENT
Insulate indoor drain pipes completely.
Insulate the connection with the indoor unit. Incomplete
insulation could result in condensation forming.
Make sure that the drain pipe slopes downwards at a
rate of 1/100 or more, do not route the drain pipe
over another pipe, and do not create a trap.
These can all cause unusual sounds.
Do not apply undue force to the drain pipe connection.
Do not leave any
undulations in the
drain pipe.
Do not let the drain
pipe slope upwards.
Do not leave the
end of the drain
hose in water.
NG
NG
NG
Heat insulator
Hard polyvinyl chloride pipe
Drain pan
Adhesion for hard polyvinyl
chloride pipe used
Drain hose
Pipe hole
(Grading downward to outdoor side)
Indoor
side
Outdoor side
Piping and Insulation
Arrange for the following materials on site for the pipe installation and insulation work.
Pipe and Drain hose formation
The drain pipe can be routed out of the rear, left, or right side of the unit.
When routing the drain pipe out the left or right side, align the pipe
and drain hose as shown in the figure at right.
Make sure that the hose does not stick out the rear of the unit.
When extending the drain hose, make the connection as shown in the
figure at right.
REQUIREMENT
Using adhesive agent for vinyl chloride, connect the hard vinyl
chloride pipes certainly so that water does not leak.
It requires several times to dry and harden the adhesive agent.
(Refer to Guide Manual of the adhesive agent.) In this time, be sure
not to apply force to the connecting section with the drain pipes.
Because the drain is a gravity drain, the pipes outside of the unit must
have a downward slope.
Once the piping work is complete, pour water in the drain pan and make
sure that the water drains completely.
Installation of remote controller (Sold separately)
For installation of the wired remote controller, follow the Installation Manual attached with the remote controller.
For installation of the wireless remote controller, follow to the Installation Manual attached to the remote controller.
Do not put the woreless remote controller on the place where is exposed to direct sunlight or near a stove, etc.
Operate the remote controller, check the indoor unit surely receives the signal, and then install the remote
controller. (Wireless type)
Install the remote controller 1m apart from the devices such as TV or stereo.
(Image may be disturbed or noise may be output.) (Wireless type)
Piping
Heat insulator
Hard polyvinyl chloride pipe :nominal dia. (inner dia.) ; Ø20mm
Vesicant polyethylene : Thickness ; 10mm
Communication
wires for control
Pipe
(Liquid side)
Tape
Pipe
(Gas side)
Lower cabinet
Drain hose