WIRING DIAGRAM
© COPYRIGHT 2008 PECO, INC. ALL RIGHTS RESERVED. P/N 69289 3220-2083 REV 0 PAGE 3
OUTPUT CONFIGURATION
A table is provided on the inside of the base to docu-
ment the function of various outputs. The function of
congurable outputs should be lled in when the unit is
installed.
JP4 JUMPER SELECTION
This jumper is temporarily installed at initial power
up to recongure outputs 3 through 6. See Output
Conguration.
JP3 JUMPER SELECTION
This jumper is shipped normally open. Placement
of a jumper onto both pins allows for Occupancy
Detection/ Door switch and Door Switch Only
Operation.
JP1 JUMPER SELECTION
Removing this jumper allows the sensor to be lo-
cated in a remote location. Accessory remote probe
sensors are available in standard 60” lengths but
can be extended to meet application requirements.
SWITCH
24V
110-
277V
HIGH -VOLTAGE -REMOVE POWER BEFORE SERVICING
CAUTION:
JP1
JP3
JP4
JP1 JUMPER
JP3 JUMPER
JP4 JUMPER
CIRCUIT BOARD
In Cover
SWITCH POSITION
This switc h is p laced in the 24V positio n a t the
factor y. Thi s thermostat will not functio n
properly if located in 110-277V positio n
INPUT
VOLTAGE
OUTPUT RA TINGS
24 VAC
PILOT
DUTY
24 VA
VOLTAGE
24 VAC