Panasonic Indoor Unit Outdoor Unit CS-E9NKUAW CS-E12NKUAW CU-E9NKUA CU-E12NKUA Air Conditioner User Manual


 
70
16.4.23 F95 (Cooling High Pressure Abnormality)
Malfunction Decision Conditions
During operation of cooling, when outdoor unit heat exchanger high temperature data (141.8°F) is detected by the
outdoor pipe temperature sensor.
Malfunction Caused
Outdoor pipe temperature rise due to short circuit of hot discharge air flow.
Outdoor pipe temperature rise due to defective of outdoor fan motor.
Outdoor pipe temperature rise due to defective outdoor pipe temperature sensor.
Outdoor pipe temperature rise due to defective outdoor unit PCB.
Troubleshooting