Panasonic CU-S9NKU-1 Air Conditioner User Manual


 
54
12.9 Outdoor Air Temperature Control
The compressor operating frequency is regulated in accordance to the outdoor air temperature as shown in the
diagram below.
This control will begin 1 minute after the compressor starts.
Compressor frequency will adjust based on outdoor air temperature.
12.10 Cooling Overload Control
Pipe temperature limitation / restriction.
o Detects the outdoor pipe temperature and carry out restriction / limitation below (Limit the compressor
operation frequency)
o The compressor stops if outdoor pipe temperature exceeds 141.8°F (for S9NK and S12NK), 145.4°F (for
S18NK and S22NK).
o If the compressor stops 4 times in 20 minutes, Timer LED blinks (“F95” indicated: Outdoor high pressure rise
protection)
12.11 Freeze Prevention Control
When indoor heat exchanger temperature is lower than 32°F continuously for 6 minutes, compressor will stops
operation.
Compressor will resume its operation 3 minutes after the indoor heat exchanger is higher than 55.4°F.
At the same time, indoor fan speed will be higher than during its normal operation.
If the indoor heat exchanger temperature is higher than 55.4°F for 5 minutes, the fan speed will return to its
normal operation.
12.12 Freeze Prevention Control 2
Control start conditions
o During Cooling operation and soft dry operation
During thermo OFF condition, indoor intake temperature is less than 50°F or
Compressor stops for freeze prevention control
o Either one of the conditions above occurs 5 times in 60 minutes.
Control contents
o Operation stops
o Timer LED blinks and “H99” indicated
12.13 Dew Prevention Control
To prevent dew formation at indoor unit discharge area.
This control will be activated if:
o Cooling mode or Quiet mode is activated.
o Remote control setting temperature is less than 77°F.
o Fan Speed is at CLo or QLo.
o Room temperature is constant (±33.8°F) for 30 minutes.
o Compressor is continuously running.
Fan speed will be adjusted accordingly in this control.
o Fan speed will be increased slowly if the unit is in quiet mode but no change in normal cooling mode.
Free
Limited Frequency
Outdoor air temperature
100.4°F or 77°F (For S18/22NK)
98.6°F or 71.6°F (For S18/22NK)