Panasonic CS-E18NKUA Air Conditioner User Manual


 
49
15.4.3 H16 (Outdoor Current Transformer Open Circuit)
Malfunction Decision Conditions
A current transformer (CT) is detected by checking the compressor running frequency ( rated frequency) and
CT detected input current (less than 0.65A) for continuously 20 seconds.
Malfunction Caused
CT defective
Outdoor PCB defective
Compressor defective (low compression)
Troubleshooting