Panasonic CS-E12NKUAW Air Conditioner User Manual


 
38
14.1.5 Compressor Overheating Prevention Control
Instructed frequency for compressor operation will be regulated by compressor discharge temperature. The
changes of frequency are as below.
If compressor discharge temperature exceeds 224.6°F, compressor will be stopped, occurs 4 times per 20
minutes, timer LED will be blinking. (“F97” is indicated.)
14.1.6 Low Pressure Prevention Control (Gas Leakage Detection)
Control start conditions
o For 5 minutes, the compressor continuously operates and outdoor total current is between 0.64A and 0.85A.
o During Cooling and Soft Dry operations:
Indoor suction temperature - indoor piping temperature is below 39.2.°F.
o During Heating operations:
Indoor piping temperature - indoor suction is under 41°F.
Control contents
o Compressor stops (and restart after 3 minutes).
o If the conditions above happen 2 times within 20 minutes, the unit will:
Stop operation
Timer LED blinks and “F91” indicated.
14.1.7 Low Frequency Protection Control 1
When the compressor operates at frequency lower than 24Hz continued for 240 minutes, the operation frequency
will be changed to 25Hz for 2 minutes.
14.1.8 Low Frequency Protection Control 2
When all below conditions comply, minimum limit of compressor will be set.
Temperature, T, for: Cooling / Soft Dry Heating
Indoor intake air (°F) T < 57.2 or T 86 -
Outdoor air (°F) T < 55.4 or T 100.4 T < 57.2 or T 82.4
Indoor heat exchanger (°F) T < 86 T 32
14.2 Protection Control For Cooling & Soft Dry Operation
14.2.1 Outdoor Air Temperature Control
The maximum current value is regulated when the outdoor air temperature rise above 57.2°F in order to avoid
compressor overloading.