Panasonic 6367 Smoke Alarm User Manual


 
All technical features and data are subject to changes without notice, resulting from continuous development and improvement.
Product Leaflet Date of issue Revision / Date of revision
MEW00435 2004-02-05 2 / 2006-08-31
Type numbers
6367 Duct detector chamber (NOTE! Detector & base have to be ordered
separately).
6371-06 Venturi pipe 0.6 m (Incl. end plug.)
6371-15 Venturi pipe 1.5 m (Incl. end plug, plastic gasket and membrane gland TET
26-35.)
6371-28 Venturi pipe 2.8 m (Incl. end plug, plastic gasket and membrane gland TET
26-35.)
6372 Bracket
6373 Booster fan (ext. 24 V AC, 50 mA required)
6374 Filter
Left: How to suit the pipe to different widths of the ventilation duct. Right: The Bracket 6372.
Attached with each Duct detector chamber are detailed mounting and installation instructions.
Technical data
Duct air flow velocity (m/s) 0.2 to 15
Ambient temperature (°C)
operating
storage
-10 to +50
-25 to +75
Ambient humidity (% RH) max. 95, non condensing
Ingress Protection rating IP54
Size L x W x H (mm) 287 x 150 x 110 (the housing only)
Weight (g) 680 (the housing only)
Construction / Colour ABS / Grey (RAL7035)
Compression glands M16x1.5 for cable Ø=3-10 mm
Approvals CE; EN 54
See also Product Leaflets / Technical data for the base and the detector to be used.
6367 can be mounted vertical or
horizontal on the duct and
3 x the duct diameter before
or
5 x the duct diameter after
a
disturbance (i.e. a bend, a filter or
a damper.