Panasonic 6275 Smoke Alarm User Manual


 
All technical features and data are subject to changes without notice, resulting from continuous development and improvement.
Product Leaflet Date of issue Revision / Date of revision
MEW00012 2000-05-15 5 / 2006-08-31
Type numbers
6275
Heat detector, fixed temperature 60°C, latching
6276
Heat detector, fixed temperature 80°C, latching
Technical data
Voltage (V DC)
rated
allowed
normal
24
12-30
24
Current consumption at nom. volt.
(mA)
quiescent (detector only)
active (detector only)
Depending on the type of base it is plugged into. For more details, see
the base respectively.
0
Max. 70 (Current limitation in all EBL equipment)
Ambient temperature (°C)
operating
storage
6275 / 6276
-10 to +40 / -10 to +60
-25 to +70 / -25 to +70
Ambient humidity (% RH) max. 95, non condensing
Ingress Protection rating (estimated) IP22
Alarm temp. (fixed temp.)
60°C (6275), 80°C (6276)
Weight, detector only (g) 70
Colour grey (N8, Munsell colour code)
Approvals CE, EN54-5, response grade 1 (6275)
CE, EN54-8, temp. range 1 detector (6276)