Panasonic 4313 Smoke Alarm User Manual


 
All technical features and data are subject to changes without notice, resulting from continuous development and improvement.
Product Leaflet Date of issue Revision / Date of revision
MEW00853 2007-01-11 1 / 2008-09-24
Type number
4313 Analog base with isolator
3390 Label holder (100 holders per packet, excl. labels)
3391 Labels for 3390 (10 sheets à 132 labels)
The detector plugged in the base is
connected on the SAo side.
SAi Terminal for COM loop (in)
SAo Terminal for COM loop (out)
SB Common terminal for COM loop
in/out)
Al Address Label
Lss Locking screw stopper (for detector
type 33xx and 430x respectively)
E- Terminal for external LED
E+ Terminal for external LED
LED Isolator LED (yellow)
Isolator LED: Normal state = one blink 250ms / 3s. Isolated state = two blinks 250ms / 3s.
NOTE! The LED is not visible when the detector is plugged in the base.
The base is prepared (Lss) for mechanical locking of detector with locking screw.
Terminal wire diameter 0.6 – 1.6 mm (approx. 0.3 – 2 mm
2
).
Analog detector types 33xx and 430x can be plugged in the base 4313. The position of the
detector's built-in LED is marked in the base for correct mounting position of the base.
Technical data
Voltage (V DC)
allowed
normal
12-30
24 (COM loop voltage)
Current consumption at nom. volt.
from COM loop (mA)
quiescent (excl. detector)
active (excl. detector)
Depending on the type of detector that is plugged into the base.
<
1.3
<
1.3
Ext. LED terminals
voltage (V)
max. current output (mA)
Depending on the detector plugged in the base. Normally:
5
2
Ambient temperature (°C)
Operating
storage
-10 to +50
-20 to +60
Ambient humidity (% RH) max. 95, non condensing
Ingress Protection rating (estimated) IP54
Size x H (mm)
102 x 15
Weight (g) 80
Construction / Colour ABS / Grey (N8, Munsell colour code)
Approvals 07 EC Certificate no. 0845-CPD-232.1567; EN54-17
Al
102 mm
15
6.2
Lss (430x)
73 mm
50 mm
OUT IN
E
xt.
LED
S
A
i
S
A
o
E
+
E
-
S
B
LED
Lss (33xx
)