Panasonic 2318 Smoke Alarm User Manual


 
All technical features and data are subject to changes without notice, resulting from continuous development and improvement.
Product Leaflet Date of issue Revision / Date of revision
MEW00449 2003-09-17 2 / 2006-08-31
Type number
2318 Combination heat detector
Technical data
Voltage (V DC)
rated
allowed
normal
24
15-30
24
Current consumption at nom. volt.
(mA)
quiescent (detector only)
active (detector only)
Depending on the type of base it is plugged into. For more details see
EBL512 Planning Instructions.
0.03
min. 3
Ambient temperature (°C)
operating
storage
-10 to +50
-25 to +70
Ambient humidity (% RH) max. 95, non condensing
Ingress Protection rating (estimated) IP51
Alarm temp. (fixed temp. part)
58°C
Weight (g) 85
Colour grey (N8, Muncell colour code)
Approvals CE; EN54/5, response grade 1.