Panasonic 1826 Smoke Alarm User Manual


 
All technical features and data are subject to changes without notice, resulting from continuous development and improvement.
Product Leaflet Date of issue Revision / Date of revision
MEW00277 2003-04-15 5 / 2008-08-18
Type numbers
1826 External Fire Brigade Panel. 1826SE / 1826CC: Designation texts on the front in
Swedish / see below. NOTE! In Swedish convention (SBF): No "General fault"
presentation.
1835 Printer for External Fire Brigade Panel 1826
1582 External FBP interface board. (Required in EBL512 / 500 when SW mode 1826/28 –
1582 2nd Cab shall be used.)
1587 External FBP / DU interface board. (Required in EBL512 when SW mode 1826/28 –
1587 2nd Cab shall be used. EBL512 software V>
2.3.2
1
required.)
2431 Connection board. (Required in EBL1000. SW mode 1826/28 – 1582 2nd Cab only.)
4552 RS485 Transceiver component / comm. module. (Required in EBL128. SW mode
1826/28 – 1587 2nd Cab only. EBL128 software V>
1.0.5
1
required.)
1
Only required if the new function ("General fault" presentation) shall be used.
NOTE! The number of ext. FBPs that can be power supplied via the c.i.e. / board / external power
supply, is depending on if each 1826 unit has a printer or not, as well as all other units connected to the
same c.i.e. / board / external power supply.
2
Up to 1200 m cable can be used.
1826CC is a unit with a neutral front
where the designation texts by production are made separately and
put into a transparent "text slot" for the LED and push button respectively. CC=Country Code.
The ext. FBP 1826 can run in one of two different SW modes:
a) 1826 in SW mode 1826/28 – 1587
2nd Cab has the highest performance with regard to
functionality, response time, ability to store fire alarms, etc. and is intended to succeed the ext. FBP 2426
(1826+printer 1835 will succeed the ext. FBP 2425) but not as a spare part
, since 1826, in this SW mode,
requires an Ext. FBP / DU interface board 1587
in the EBL512 c.i.e. and the look, dimensions, etc. are
not the same. This mode is always to be used when the ext. FBP is connected to EBL128.
b) 1826 in SW mode 1826/28 – 1582
2nd Cab has the same functionality as the ext. FBP 2426 and can
be used as a spare part
(1826+printer 1835 is a spare part for the ext. FBP 2425), i.e. the performance is
the same but the look, dimensions, etc. are not the same. 1826, in this SW mode, requires an Ext. FBP
interface board 1582 in the EBL512 / EBL500 c.i.e.
Technical data
Voltage (V DC)
rated
allowed
24
12-30
normal (in the system)
normal (in the system by battery back-up)
24
21-27
Current consumption at norm. volt. (mA)
Ext. FBP 1826
quiescent / active
Printer 1835
quiescent / active
26 (at 24 V), 48 (at 12 V) / 49 (at 24 V), 88 (at 12 V)
4 (at 24 V), 7 (at 12 V) / 161 (at 24 V), 345 (at 12 V)
Ambient temperature (°C)
operating
storage
0 to +40
-40 to +70
Ambient humidity (% RH) max. 90, non condensing
Ingress Protection rating (estimated) IP52
Size W x H x D (mm) 415 x 290 x 128
Weight (g)
Ext. FBP 1826 (excl. printer)
Printer 1835 (incl. paper roll) / paper roll
5000
345 / 110
Colour (metal cabinet / door) Light grey (NCS S 1500-N, PMS Cool grey 2) & aluminium sides.
Approvals CE; Conforms with EN54-2 and –4 whenever applicable.
Conforms with SS3654 edition 1.
2
On each 1582 board are up to eight addresses available and on each 1587 board up to sixteen addresses. In EBL128
are up to four addresses
available.