Nortec Industries NHTC Series Humidifier User Manual


 
10-10
Page 7
2008-02-18
Variable Name
R=Read
W=Write
Description LonWorks SNVT
nvoFault_x
R
Binary Value
Indicates unit fault status.
0=no fault, 1=fault.
SNVT_switch
nvoHWSensor_x
R
Binary Value
Indicates if a high-water level
condition exists in the humidifier
cylinder.
0=normal, 1=high water condition
nvoNetSensor_x
R
Binary Value
Reads configuration status for
network-enabled sensing or
control.
0=%RH or %demand input is not
from the network
1=%RH or %demand input is
from
the network
SNVT_switch
nvoDisable_x
R
Binary Value
Reads remote disable status.
0=humidifier enabled,
1=humidifier disabled by network
SNVT_switch
nvoSecurity_x
R
Binary
Indicates security loop status.
0=Sec. loop open,
1=Sec. loop closed
SNVT_switch
nvoService_x
R
Binary Value
Reads service requirement status.
0=no service required,
1=service required
SNVT_switch
nvoStatus_x
R
Binary Value
Reads humidifier status.
0=standby, 1=humidifying.
SNVT_switch
nvoConnection_x
R
Binary Value
Indicates that the Nortec Links
module is communicating with the
Humidifier
SNVT_switch
nviDisable_x
W
Binary Value
Writes remote disable status.
0=humidifier enabled,
1=humidifier disabled from
network
SNVT_switch
nviNetSensor _x
W
Binary Value
Writes configuration status for
network-enabled sensing or
control.
0=%RH or %demand input is not
from the network
1=%RH or %demand input is
from
the network
SNVT_switch