Nordyne Q4 Series Electric Heater User Manual


 
16
Q4SA-060
OUTDOOR TEMPERATURE ( °F )
70 75 80 85 90 95 100 105
Suct.
Pres.
Disch.
Pres.
Disch.
Temp.
Disch.
Pres.
Disch.
Temp.
Disch.
Pres.
Disch.
Temp.
Disch.
Pres.
Disch.
Temp.
Disch.
Pres.
Disch.
Temp.
Disch.
Pres.
Disch.
Temp.
Disch.
Pres.
Disch.
Temp.
Disch.
Pres.
Disch.
Temp.
68 192 157
70 193 165 208 164
72 194 182 210 172 226 164 239 165 252 167
74 195 199 211 187 227 178 243 168 256 175 269 171
76 195 216 213 201 229 191 245 181 260 180 273 178 287 175
78 214 215 231 204 247 195 262 188 278 183 291 181 304 179
80 232 216 249 207 265 199 280 193 295 188 309 185
82 267 210 282 203 298 197 313 192
84 300 206 315 201
86 303 216 318 210
88 320 219
Table 3a. Q4SA Cooling Charging Charts
Heat Pump in Cooling
* Note: All pressures are listed in
psig. and all temperatures in deg. F.
Shaded Boxes indicate flooded conditions
Rated Design Values. Suction Pressure will be lower than design value if indoor air
flow, entering dry bulb, or entering wet bulb temperatures are lower than design.
Discharge temperatures greater than charted values indicates a refrigerant
undercharge.