Monessen Hearth GCUF Series Indoor Fireplace User Manual


 
8 71D0530
9"
Minimum
42"
Minimum
9"
Minimum
Ensure that minimum clearances shown in Figures 4 through 8 are maintained. Left and right clearances are determined
when facing the front of the firebox.
Follow these instructions carefully to ensure safe installation. Failure to follow these requirements may create a
fire hazard.
1. Sidewall clearances: The clearance from the inside of the appliance to any combustible wall should not be
less than 9". See Figure 4.
2. Ceiling clearance: The ceiling must be at least 42” from the top of the firebox opening. See Figure 4.
3. Back wall clearance: The appliance may be placed against a combustible back wall.
Figure 4 - Clearance and Height Requirements
CLEARANCES AND HEIGHT REQUIREMENTS