Make sure you have the items listed below before installing appliance.
External regulator (supplied by installer) Piping (check local codes) Test gauge connection*
Sealant (resistant to propane/LP gas) Sediment trap (optional but recommended)
Tee joint Pipe wrench
approved flexible gas line with gas connector (if allowed by local codes — not provided)
* A CSA design-certified equipment shutoff valve with 1/8" NPT tap is an acceptable alternative to test
gauge connection. Purchase the CSA design-certified equipment shutoff valve from your dealer.
For propane/LP connections only, the installer must supply an external regulator. The external regulator will
reduce incoming gas pressure. You must reduce incoming gas pressure to between 11 and 13 inches of wa-
ter. If you do not reduce incoming gas pressure, burner system regulator damage could occur. Install external
regulator with the vent pointing down as shown in Figure 14. Pointing the vent down protects it from freezing
rain or sleet.
&0
EXTERNALREGULATOR

External
Regual-
tor
Vent
Pointing
Down
100 gal. (min.
Propane/LP
Supply Tank
FP1930
Figure 14 -
External Regulator with Vent Pointing Down
(Propane/LP Only)









     


Use proper gas type for the fireplace you are installing. If you have conflicting gas type, do not install
fireplace. See dealer where you purchased the fireplace for proper fireplace according to your gas
type.



   


    
    
     
    


When using copper or flex connectors use only fittings
approved for gas connections. The gas control inlet is
3/8" NPT.