Mitsumi electronic MSZ-DNA Air Conditioner User Manual


 
26
MXZ-3A30NA-
1
MXZ-4A36NA MXZ-3B24NA MXZ-3B30NA MXZ-4B36NA
Exclusive LEV
Standard opening (pulse)
LEV Opening (code)
12345678910
COOL 126 130 134 138 150 160 170 180 190 200
HEAT 248 248 258 266 274 280 286 292 300 306
Difference in capacity
Difference in operation number
Code3,4 Code5,6 Code7,8
Code9,10 Code11,12 Code13,14
Code15or above
23
4(MXZ-4A/4B)
COOL 3 6 9 12 15 25 35 -20 -30 -30
HEAT 3 6 9 52 55 65 75 -4 -8 -12
Receiver LEV
Standard opening (pulse)
LEV Opening (code)
12345678910
COOL 270 280 290 300 310 320 330 340 350 360
HEAT 140 152 160 170 180 200 224 244 274 280
Operation number
Difference in operation number
23
4(MXZ-4A/4B)
COOL 28 56 84
HEAT -45 -60 -60
Capacity code 3 4 7 9 10 12
Indoor unit 06 09 12 15 17 24
MXZ-2A20NA-
1
,
2
MXZ-2B20NA
MXZ-2B20NA-
1
Exclusive LEV
Standard opening (pulse)
LEV Opening (code)
12345678910
COOL 120 130 136 146 156 160 170 180 190 200
HEAT 248 248 258 266 274 280 286 292 300 306
Difference in capacity
Difference in operation number
Code3,4 Code5,6 Code7,8
Code9,10 Code11,12 Code13,14
Code15or above
2
COOL 3 6 9 12 15 25 35 -20
HEAT 3 6 9 52556575 30
Receiver LEV
Standard opening (pulse)
LEV Opening (code)
12345678910
COOL 140 150 160 170 180 190 200 200 200 200
HEAT 80 84 90 110 120 130 140 150 160 170
Operation number
Difference in operation number
2
COOL -20
HEAT 30