Mitsubishi P96 Air Conditioner User Manual


 
[ VIII Test Run Mode ]
- 137 -
HWE09120 GB
Operation
Outdoor unit model
PUHY-P216TSJMU-A
PUHY-P96TJMU-A PUHY-P120TJMU-A
Operating
conditions
Ambient
tempera-
ture
Indoor
DB/WB
26.7°C /19.4°C [80 °F/67 °F]
Outdoor
35°C/ - [95°F/ - ]
Indoor
unit
No. of connected
units
Unit
6
No. of units in opera-
tion 6
Model - 06/36/36/36/48/48
Piping
Main pipe
m [ft]
5[16-3/8]
Branch pipe 10 [32-3/4]
Total pipe length 65 [213-1/4]
Fan speed - Hi
Amount of refrigerant
kg
[lbs-oz] 23 [50]
Outdoor
unit
Electric current A 51.2
Voltage V 230
Compressor frequency Hz 65 74
LEV open-
ing
Indoor unit
Pulse
222/325/325/325/387/387
SC (LEV1) 159 237
LEV2 2100 2100
Pressure
High pressure (after O/S)/low
pressure (before accumulator)
MPa
[psi] 2.88/0.87 [417/127] 2.88/0.87 [417/127]
Temp. of
each sec-
tion
Outdoor
unit
Discharge (TH4)
°C [°F]
74 [165] 73 [163]
Heat exchanger out-
let (TH3) 46 [115] 40 [104]
Accumulator inlet 10 [50] 10 [50]
Accumulator outlet 10 [50] 10 [50]
SCC outlet (TH6) 26 [79] 20 [68]
Compressor inlet 14 [57] 15 [59]
Compressor shell
bottom 38 [100] 42 [108]
Indoor
unit
LEV inlet 22 [72] 22 [72]
Heat exchanger
outlet 10 [50] 10 [50]