Mitsubishi P336 Air Conditioner User Manual


 
[ VIII Test Run Mode ]
- 138 -
HWE09120 GB
Operation
Outdoor unit model
PUHY-P240TSJMU-A
PUHY-P120TJMU-A PUHY-P120TJMU-A
Operating
conditions
Ambient
tempera-
ture
Indoor
DB/WB
26.7°C /19.4°C [80 °F/67 °F]
Outdoor
35°C/ - [95°F/ - ]
Indoor
unit
No. of connected
units
Unit
6
No. of units in opera-
tion 6
Model - 18/36/36/36/48/48
Piping
Main pipe
m [ft]
5 [16-3/8 ]
Branch pipe 10 [32-3/4 ]
Total pipe length 65 [213-1/4]
Fan speed - Hi
Amount of refrigerant
kg
[lbs-oz] 25 [55]
Outdoor
unit
Electric current A 56.8
Voltage V 230
Compressor frequency Hz 74 74
LEV open-
ing
Indoor unit
Pulse
362/325/325/325/387/387
SC (LEV1) 237 237
LEV2 2100 2100
Pressure
High pressure (after O/S)/low
pressure (before accumulator)
MPa
[psi] 2.92/0.90 [424/131] 2.92/0.90 [424/131]
Temp. of
each sec-
tion
Outdoor
unit
Discharge (TH4)
°C [°F]
73 [163] 73 [163]
Heat exchanger out-
let (TH3) 40 [104] 40 [104]
Accumulator inlet 10 [50] 10 [50]
Accumulator outlet 10 [50] 10 [50]
SCC outlet (TH6) 20 [68] 20 [68]
Compressor inlet 15 [59] 15 [59]
Compressor shell
bottom 42 [108] 42 [108]
Indoor
unit
LEV inlet 19 [66] 19 [66]
Heat exchanger
outlet 10 [50] 10 [50]