Mitsubishi P240 Air Conditioner User Manual


 
[ IX Troubleshooting ]
- 209 -
HWE09120 GB
1. Error Code
No ACK error
2. Error definition and error detection method
The error is detected when no acknowledgement (ACK signal) is received after the transmission. (eg. When the data is trans-
mitted six times in a row with 30 seconds interval, the error is detected on the transmission side.)
The address/attribute appeared on the display on the remote controller indicates the controller which did not provide
the response (ACK).
3. System configuration
(3) System connected to the system controllers (MELANS)
6607
Error
source
address
Error display
Detection
method
Cause Check method and remedy
System
controller
(SC)
ME remote
controller
(RC)
MA remote
controller
(MA)
No acknowl-
edgement
(ACK) at IC
transmission to
SC
1. Error display on some displays on
ME remote controllers
Check (1) - (3) on the left.
(1) Faulty wiring of the transmission
line for ME remote controller
(2) Disconnection or contact failure of
the transmission connector for ME
remote controller
(3) ME remote controller failure
2. Error occurrence on all IC in the
system with one outdoor unit
1) Check the LED display for
troubleshooting on the out-
door unit.
(1) An error is found by the outdoor
unit.
Total capacity error (7100)
Capacity code error (7101)
Error in the number of connected
units (7102)
Address setting error (7105)
If an error is found, check
the check code definition,
and correct the error.
If no error is found, check
the cause 2)
(2) Disconnection or short circuit of the
transmission line for the outdoor
unit on the terminal block for cen-
tralized control line connection
(TB7)
2) Check (2) - (4) on the left.
(3) Turn off the power source of the
outdoor unit
(4) Malfunction of electrical system for
the outdoor unit
3. Error display on all displays on ME
remote controllers
Check (1) - (4) on the left
(1) Same causes as (1) - (4) described
in 2.
(2) When the power supply unit for
transmission lines is used and the
male power supply connector is
connected to the female power sup-
ply switch connector (CN40) for the
transmission line for centralized
control
(3) Disconnection or shutdown of the
power source of the power supply
unit for transmission line
(4) System controller (MELANS) mal-
function