Mitsubishi P144T(Y)JMU-A PUHY-P168 Air Conditioner User Manual


 
[ VIII Test Run Mode ]
- 131 -
HWE09120 GB
[7] Standard Operation Data (Reference Data)
1. Single unit
(1) Cooling operation
Operation
Outdoor unit model
PUHY-P72TJMU-A PUHY-P96TJMU-A
Operating
conditions
Ambient
tempera-
ture
Indoor
DB/WB
26.7°C/19.4°C [80°F/67°F] 26.7°C/19.4°C [80°F/67°F]
Outdoor
35°C/ - [95°F/ - ] 35°C/ - [95°F/ - ]
Indoor
unit
No. of connected
units
Unit
22
No. of units in opera-
tion 2 2
Model - 36/36 48/48
Piping
Main pipe
m [ft]
5 [16-3/8 ] 5 [16-3/8 ]
Branch pipe 10 [32-3/4 ] 10 [32-3/4 ]
Total pipe length 25 [82] 25 [82]
Fan speed - Hi Hi
Amount of refrigerant
kg
[lbs-oz] 11 [24] 9 [19]
Outdoor
unit
Electric current A 14.6 23.4
Voltage V 230 230
Compressor frequency Hz 52 65
LEV open-
ing
Indoor unit
Pulse
325/325 387/387
SC (LEV1) 80 100
LEV2 2100 2100
Pressure
High pressure (after O/S)/low
pressure (before accumulator)
MPa
[psi] 2.59/0.96 [376/139] 2.83/0.84 [410/122]
Temp. of
each sec-
tion
Outdoor
unit
Discharge (TH4)
°C [°F]
69 [156] 74 [165]
Heat exchanger out-
let (TH3)
44 [111] 46 [115]
Accumulator inlet 10 [50] 10 [50]
Accumulator outlet 10 [50] 10 [50]
SCC outlet (TH6) 24 [75] 26 [79]
Compressor inlet 17 [63] 14 [57]
Compressor shell
bottom
47 [117] 38 [100]
Indoor
unit
LEV inlet 23 [73] 25 [77]
Heat exchanger
outlet
10 [50] 10 [50]