GENERAL SPECIFICACIONS FOR ALL MODELS
Main Optional Parts
ledoM noitpircseDsledomelbacilppA
DA527-CAP )stes01(retpadArellortnoCetomeRelpitluM New A/K control
PAC-SE55RA-E Timer Adapter New A/K control
MAC-397IF-E MA & Control Terminal Interface New A/K control
New A/K control
PAC-SE41TS-E rosneSetomeR
E-SD64AS
-CAPtekcoSniarD 2.5~4-HUP
E-SD74AS-CAPtekcoSniarD6/5-HUP
D-GS292-CAPediuGteltuOriA 2.5~6-HUP
E-S05-DDSesUniwTrofepiPnoitubirtsiD 5/6-HUP
E-MD58ES-CAPmsinahceMpU-tfiLniarD3-HCP
E-M
A
AD68ES-CAPmsinahceMpU-tfiLniarD6~4-HCP
E-FK18ES-CAPretliFycneiciffEhgiH 3/4-HCP
E-FK28ES-CAPretliFycneiciffEhgiH 5/6-HCP
PAR-SL99B-E Wireless Remote Controller PCH series
PAR-SL97A-E Wireless Remote Controller PLH series
tnemelEretliFycneiciffEhgiH
PAC-SG01KF PLH series
etalPrettuhSteltuOriA
PAC-SG06SP-E PLH series
tnemesaCnoitcnuF-itluM
PAC-SG03TM-E PLH series
Refrigerant Piping
Between indoor & outdoor units Pipe size O.D., mm
Models
Max. hei
g
ht difference, m
Max. piping length, m
Max. number of bends
Liquid Gas
PLH-3AAK, PKH-3FAK,
PCH-3GAK, PEH-2.5EAK, PEH-3EAK
50 50 15 Ø 9.52 Ø 15.88
PKH-4FAK PLH-4/5/6AAK,
PCH-4/5/6GAK, PEH-4/5/6EAK
50 50 15 Ø 9.52 Ø 19.05
Optional Refrigerant Pipes
Pipe length
Part number
5m (16ft) PAC-05FFS-E PAC-SC51PI-E
7m (23ft) PAC-07FFS-E PAC-SC52PI-E
10m (33ft) PAC-10FFS-E PAC-SC53PI-E
15m (49ft) PAC-15FFS-E PAC-SC54PI-E
Connection method Flared-flared Flared-flared
Pipe size OD, mm (ft) Liquid: Ø 9.52 (3/8) Gas: Ø 15.88 (5/8) Liquid: Ø 9.52 (3/8) Gas: Ø 19.05 (3/4)
Applicable models PKH-3FAK, PLH-3AAK, PCH-3GAK, PEH-2.5EAK, PEH-3EAK PKH-4FAK, PLH-4/5/6AAK, PCH-4/5/6GAK, PEH-4/5/6EAK
Additional Refrigerant Charge [R-22: kg]
Piping length (one-way)
Models
5m 10m 15m 20m 25m 30m 35m 40m 45m 50m
PUH-2.5AKA 0 0 0 0 0 0 0.2 0.2 0.5 0.5
PUH-3VKA/PUH-3YKA 0 0 0 0 0 0 0.2 0.2 0.5 0.5
PUH-4YKSA 0 0 0 0 0 0 0.3 0.3 0.6 0.6
PUH-5YKSA 0 0 0 0 0 0 0.3 0.3 0.6 0.6
PUH-6YKSA 0 0 0 0 0 0 0.3 0.3 0.6 0.6
Guaranteed Operating Range
Limits Indoors Outdoors
Lower 21ºC DB, 15.5ºC WB -5ºC DB
Cooling
Upper 35ºC DB, 22.5ºC WB 46ºC DB
Lower 20ºC DB -8.5ºC DB, -9.5ºC WB
Heating
Upper 27ºC DB 21ºC DB, 15.5ºC WB
Notes for All Specifications
Rating conditions:
Cooling - Indoor 27ºCDB, 19ºCWB; Outdoor 35ºCDB
Heating - Indoor 20ºCDB ; Outdoor 7ºCDB,6ºCWB
Data based on indicated voltage
Indoor unit : 1-ph, 240V, 50Hz
Outdoor unit: 1-ph, 240V, 50Hz/3-ph, 415V, 50Hz
Refrigerant piping length (one-way): 5m (16ft)
Refrigerant charge is suitable for 5m piping length.
Cooling Capacity Correction Factors
Models Correction factors (Cooling / Heating)
One-way piping length, m 5 10 15 20 25 30 35 40 45 50
PEH-2.5EAK
1.00/1.00 0.989/1.00 0.980/1.00
0.970/1.00
0.960/1.00 0.950/1.00
0 .9 4 0 /0 . 99 8 0 .9 3 0 /0 . 99 5 0 .9 2 0 /0 . 99 3 0 .9 10 /0 . 99 0
PKH-3FAK, PCH-3GAK,
PLH-3AAK, PEH-3EAK
1.00/1.00
0.981/1.00 0.968/1.00 0.952/1.00 0.940/1.00 0.925/1.00
0 .9 1 3 /0 . 99 8 0 .9 0 0 /0 . 99 5 0 .8 8 6 /0 . 99 3 0 .8 74 /0 . 99 0
PKH-4FAK PCH-4GAK,
PLH-4AAK, PEH-4EAK
1.00/1.00
0.989/1.00 0.980/1.00 0.970/1.00 0.960/1.00 0.950/1.00
0 .9 4 0 /0 . 99 8 0 .9 3 0 /0 . 99 5 0 .9 2 0 /0 . 99 3 0 .9 10 /0 . 99 0
PCH-5GAK PLH-5AAK,
PEH-5EAK
1.00/1.00
0.981/1.00 0.968/1.00 0.952/1.00 0.940/1.00 0.925/1.00
0 .9 1 3 /0 . 99 8 0 .9 0 0 /0 . 99 5 0 .8 8 6 /0 . 99 3 0 .8 74 /0 . 99 0
PCH-6GAK, PLH-6AAK
PEH-6EAK
1.00/1.00
0.975/1.00 0.955/1.00 0.935/1.00 0.918/1.00 0.900/1.00
0 .8 8 4 /0 . 99 8 0 .8 6 9 /0 . 99 5 0 .8 5 5 /0 . 99 3 0 .8 40 /0 . 99 0