Specications System Module 1 Module 2
Unit Type PURY-P192YSKMU-A (-BS) PURY-P96YKMU-A (-BS) PURY-P96YKMU-A (-BS)
Nominal Cooling Capacity (460V) Btu/h 192,000 96,000 96,000
Nominal Heating Capacity (460V) Btu/h 215,000 108,000 108,000
Operating Temperature Range *1
Cooling (Outdoor) *2
Refer to Module Data
23~115° F (-5~46° C) DB
Heating (Outdoor) -4~60° F (-20~15.5° C) WB
External Dimensions (H x W x D)
In.
mm
Refer to Module Data
64-31/32 x 48-1/16 x 29-5/32
1,650 x 1,220 x 740
64-31/32 x 48-1/16 x 29-5/32
1,650 x 1,220 x 740
Net Weight Lbs. / kg 1,148 (520) 574 (260) 574 (260)
External Finish
Refer to Module Data Pre-coated galvanized steel sheet
Electrical Power Requirements Voltage, Phase, Hertz Refer to Module Data** 460V, 3-Phase, 60Hz
Minimum Circuit Ampacity (MCA) A Refer to Module Data** 15 15
Maximum Fuse Size A Refer to Module Data** 20 20
Piping Diameter
F r o m T w i n n i n g K i t t o I n d o o r U n i t s
(Brazed) (In. / mm)
Liquid (High Pressure) 7/8 (22.2) Brazed
Refer to System Data
Gas (Low Pressure) 1-1/8 (28.58) Brazed
Max. Total Refrigerant Line Length Ft. 2,461
Refer to System Data
Max. Refrigerant Line Length
(Between ODU & IDU)
Ft. 541
Max. Control Wiring Length Ft. 1,650
Indoor Unit
Total Capacity 50~150% of ODUs Refer to System Data
Model / Quantity P06~P96/1~48 Refer to System Data
Sound Pressure Level dB(A) 61 Refer to System Data
Fan
Type x Quantity
Refer to Module Data
Propeller fan x 1 Propeller fan x 1
Airow Rate CFM 6,200 6,200
External Static Pressure In. WG (Pa) Refer to Module Data Selectable; 0, 0.12 or 0.24”WG; factory set to 0”W.G.
Compressor Operating Range 8% to 100% Refer to System Data
Compressor Type x Quantity Refer to Module Data
Inverter-driven Scroll
Hermetic x 1
Inverter-driven Scroll
Hermetic x 1
Refrigerant Refer to Module Data
R410A x 26 lbs + 1 oz
(11.8 kg)
R410A x 26 lbs + 1 oz
(11.8 kg)
Protection Devices
High Pressure
Refer to Module Data
High pressure sensor, High
pressure switch at 4.15 MPa
(601 psi)
High pressure sensor, High
pressure switch at 4.15 MPa
(601 psi)
Inverter Circuit
(Comp. / Fan)
Over-current protection Over-current protection
Fan Motor Thermal switch Thermal switch
AHRI Ratings
(Ducted/Non-Ducted)
EER 11.6 / 11.9
Refer to System DataIEER 19.3 / 18.2
COP 3.64 / 3.47
Simultaneous Rating
(Ducted/Non-Ducted)
SCHE *3 17.40 / 21.81 Refer to System Data
Blue Fin Anti-corrosion Protection: Cellulose- and polyurethane-resin coating treatment applied to condenser coil that protects it from air contaminants
Standard: ≥1μm thick; Salt Spray Test Method - no unusual rust development to 480 hours.
Sea Coast (BS): ≥1μm thick; Salt Spray Test Method - no unusual rust development to 960 hours.
Outdoor Unit: 16-TON PURY-P192YSKMU-A (-BS)
(Consists of Two PURY-P96YKMU-A (-BS) and One CMY-R100CBK2 Twinning Kit)
UNIT OPTION
□ Standard Model……..….........…...………….PURY-P192YSKMU-A
□ Sea Coast (BS) Model………....……….PURY-P192YSKMU-A-BS
OUTDOOR VRF HEAT PUMP WITH HEAT RECOVERY
SYSTEM FEATURES
• INVERTER-driven compressor
• Air-source, simultaneous cooling and heating
• Long line lengths - for details see Engineering Manual
• Connects to CITY MULTI indoor units
• Controlled via CITY MULTI Controls Network
NOTES:
*1. Harsh weather environments may demand performance enhancing equipment.
Ask your Mitsubishi Electric representative for more details about your region.
*2. For details on extended cooling operation range down to -10° F DB, see Low Ambient Kit Submittal.
*3. Simultaneous Cooling and Heating Efciency
** Each individual module requires a separate electrical connection.
Refer to electrical data for each individual module.
OPTIONAL PARTS
□ Twinning Kit (required)..............................................…CMY-R100CBK2
□ Joint Kit.............................…for details see Pipe Accesories Submittal
□ Joint Adapter Kit................…for details see Pipe Accesories Submittal
□ Low Ambient Kit ...............…..for details see Low Ambient Kit Submittal
□ Snow/Hail Guards Kit......…for details see Snow/Hail Guards Kit Submittal