Outdoor Unit: PUHY-P168TSHMU-A – DIMENSIONS
920 (36-1/4)760 (29-15/16)
30 (1-3/16)
920 (36-1/4)
Intake
air
Outdoor unit 2Outdoor unit 1Discharge air
Intake
air
Left view
Front view
Note 1. Connect the pipes as shown in the figure above. Refer to the table above for the pipe size.
2. Twinning pipes should not be tilted more than 15 degrees from the horizontal plane.
Be sure to see the Installation Manual for details of Twinning pipe installation.
3. The pipe section before the Twinning pipe (sections "a" and "b" in the figure) must have at least 500mm (19-11/16) of straight section
(*including the straight pipe that is supplied with the Twinning pipe).
4. Only use the Twinning pipes manufactured by Mitsubishi (optional parts).
Twinning pipe ~ Outdoor unit
Unit model
P96
P72
Liquid
Gas
c or ed or f
bGas
Liquid
Outdoor unit 2
ø9.52 (3/8)
ø9.52 (3/8)ø19.05 (3/4)
ø22.2 (7/8)
1650 (64-31/32)
Intake
air
To indoor unit
c
d
b
a
f
e
Gas Twinning pipe <optional parts>
Liquid Twinning pipe <optional parts>
To indoor unit
Twinning pipe connection size
PUHY-P144TSHMU-A(-BS)
PUHY-P72THMU-A(-BS)
PUHY-P72THMU-A(-BS)
Package unit name
Component unit name
Outdoor Twinning Kit (optional parts)
Indoor unit ~ Twinning pipe
Outdoor unit 1
ø28.58 (1-1/8)
ø15.88 (5/8)
PUHY- P72THMU-A(-BS)
PUHY- P96THMU-A(-BS)
PUHY- P168TSHMU-A(-BS)
CMY- Y100VBK2
a
Unit : mm(in)
ø12.7 (1/2)