Mitsubishi Electronics PUHY-P36 Air Conditioner User Manual


 
[ IX Troubleshooting ]
- 175 -
HWE08040 GB
1. Error Code
Heatsink overheat protection
2. Error definition and error detection method
When the heat sink temperature (THHS) remains at or above TOH is detected.
3. Cause, check method and remedy
Refer to section -6- "Inverter (THMU-A)" under part [4] Troubleshooting Principal Parts for error codes related to the
inverter.(page 244)
4230 (THMU-A)
Model TOH
P72, P96 models 100°C [212°F]
P120 model 90°C [194°F]
Cause Check method and remedy
(1) Fan board failure Refer to IX [4] -6- (2) [6].(page 247)
(2) Outdoor unit fan failure Check the outdoor unit fan operation.
If any problem is found with the fan operation, check the fan motor. ->Refer to
IX [4] -6- (2) [5].(page 247)
(3) Air passage blockage Check that the heat sink cooling air passage is not blocked
(4) THHS failure P72 and P96 models
1) Check for proper installation of the INV board IGBT. (Check for proper instal-
lation of the IGBT heatsink.)
2) Check for proper installation of the INV board IGBT.
->If an abnormal value appears, replace the INV board.
P120 model
3) Check the THHS sensor reading on the LED monitor.
->If an abnormal value appears, check the sensor resistance, and replace the
sensor as necessary.