Mitsubishi Electronics PUHY-P336 Air Conditioner User Manual


 
[ VIII Test Run Mode ]
- 124 -
HWE08040 GB
Operation
Outdoor unit model
PUHY-P120THMU-A
Operating
conditions
Ambient
tempera-
ture
Indoor
DB/WB
26.7°C/19.4°C [80°F/67°F]
Outdoor
35°C/ - [95°F/ - ]
Indoor
unit
No. of connected
units
Unit
3
No. of units in opera-
tion 3
Model - 36/36/36
Piping
Main pipe
m [ft]
5 [16-3/8 ]
Branch pipe 10 [32-3/4 ]
Total pipe length 35 [114-13/16 ]
Fan speed - Hi
Amount of refrigerant
kg
[lbs-oz] 15 [33]
Outdoor
unit
Electric current A 28.1
Voltage V 230
Compressor frequency Hz 74
LEV open-
ing
Indoor unit
Pulse
325/325/325
SC (LEV1) 100
LEV2 1400
Pressure
High pressure (after O/S)/low
pressure (before accumulator)
MPa
[psi] 2.92/0.90 [424/131]
Temp. of
each sec-
tion
Outdoor
unit
Discharge (TH4)
°C [°F]
73 [163]
Heat exchanger out-
let (TH3) 40 [104]
Accumulator inlet 10 [50]
Accumulator outlet 10 [50]
SCC outlet (TH6) 20 [68]
Compressor inlet 15 [59]
Compressor shell
bottom 42 [108]
Indoor
unit
LEV inlet 19 [66]
Heat exchanger
outlet 10 [50]