Mitsubishi Electronics PUHY-P312 Air Conditioner User Manual


 
[ IX Troubleshooting ]
- 202 -
HWE08040 GB
1. Error Code
No ACK error
2. Error definition and error detection method
The error is detected when no acknowledgement (ACK signal) is received after the transmission. (eg. When the data is trans-
mitted six times in a row with 30 seconds interval, the error is detected on the transmission side.)
The address/attribute appeared on the display on the remote controller indicates the controller which did not provide
the response (ACK).
3. System configuration
(3) System connected to the system controllers (MELANS)
6607
Error
source
address
Error display
Detection
method
Cause Check method and remedy
M-NET re-
mote con-
troller
(RC)
M-NET re-
mote controller
(RC)
System con-
troller (SC)
MA remote
controller (MA)
No acknowl-
edgement
(ACK) at IC
transmission to
RC
Same as grouping of units in a sys-
tem with multiple outdoor units
Same remedy as that for
grouping of units in a system
with multiple outdoor units
System con-
troller
(SC)
No acknowl-
edgement
(ACK) at
MELANS
transmission to
RC
1. Error occurrence on some IC Same remedy as that for
system with one outdoor unit
(1) Same cause as that for system
with one outdoor unit
2. Error occurrence on all IC in the
system with one outdoor unit
1) Check the LED display for
troubleshooting on the out-
door unit.
(1) An error is found by the outdoor
unit.
Total capacity error (7100)
Capacity code error (7101)
Error in the number of connected
units (7102)
Address setting error (7105)
If an error is found, check
the check code definition,
and correct the error.
If no error is found, check
the cause 2).
(2) Disconnection or short circuit of the
transmission line for the outdoor
unit on the terminal block for cen-
tralized control line connection
(TB7)
2) Check (2) - (4) on the left.
(3) Turn off the power source of the
outdoor unit
(4) Malfunction of electrical system for
the outdoor unit
3. Error occurrence on all IC Check (1) - (4) on the left.
(1) Same causes as (1) - (4) described
in 2.
(2) When the power supply unit for
transmission lines is used and the
male power supply connector is
connected to the female power
supply switch connector (CN40) for
the transmission line for central-
ized control
(3) Disconnection or shutdown of the
power source of the power supply
unit for transmission line
(4) System controller (MELANS) mal-
function