Mitsubishi Electronics PUHY-P192 Air Conditioner User Manual


 
[ VIII Test Run Mode ]
- 143 -
HWE08040 GB
Operation
Outdoor unit model
PUHY-P288TSHMU-A
PUHY-P72THMU-A PUHY-P96THMU-A
PUHY-
P120THMU-A
Operating
conditions
Ambient
tempera-
ture
Indoor
DB/WB
21.1°C/ - [70°F/ - ]
Outdoor
8.3°C/6.1°C [47°F/43°F]
Indoor
unit
No. of connected
units
Unit
6
No. of units in opera-
tion 6
Model - 48/48/48/48/48/48
Piping
Main pipe
m [ft]
5[16-3/8]
Branch pipe 10 [32-3/4]
Total pipe length 65 [213-1/4]
Fan speed - Hi
Amount of refrigerant
kg
[lbs-oz] 34 [75]
Outdoor
unit
Electric current A 67.6
Voltage V 230
Compressor frequency Hz 53 71 75
LEV open-
ing
Indoor unit
Pulse
332/332/406/406/406/406
SC (LEV1) 0
LEV2 1160 1280 1280
Pressure
High pressure (after O/S)/low
pressure (before accumulator)
MPa
[psi]
2.71/0.65 2.71/0.65 2.71/0.65
[394/95] [394/95] [394/95]
Temp. of
each sec-
tion
Outdoor
unit
Discharge (TH4)
°C [°F]
72 [162] 75 [167] 70 [158]
Heat exchanger out-
let (TH3) 0 [32] -2 [28] -1 [30]
Accumulator inlet 0 [32] -2 [28] -1 [30]
Accumulator outlet 0 [32] -2 [28] -1 [30]
Compressor inlet 0 [32] -2 [28] -1 [30]
Compressor shell
bottom 40 [104] 40 [104] 40 [104]
Indoor
unit
LEV inlet 36 [97] 37 [99] 36 [97]
Heat exchanger
inlet 70 [158] 73 [163] 69 [156]