Mitsubishi Electronics PDFY-P30NMU-E Air Conditioner User Manual


 
7
LEV
C1 3.0µF X 440V 5.0µF X 440V
5.0µF
X 440V
8.0µF
X 440V
6.0µF X 440V
MF1
PDFY-
P06,08,12
NMU-E
PDFY-
P30
NMU-E
PDFY-
P36
NMU-E
PDFY-
P48
NMU-E
PDFY-
P24,27
NMU-E
PDFY-
P15,18
NMU-E
3-2. Electrical parts specifications
Model
Parts
name
Tranrsformer T (Primary) 240V 60Hz (Secondary) (23.5V 0.9A)
TH21
Resistance 0˚C[32˚F]/15k,10˚C[50˚F]/9.6k,20˚C[68˚F]/6.3k,25˚C[77˚F]/5.4k,
30˚C[86˚F]/4.3k,40˚C[104˚F]/3.0k
Resistance 0˚C[32˚F]/15k,10˚C[50˚F]/9.6k,20˚C[68˚F]/6.3k,25˚C[77˚F]/5.4k,
30˚C[86˚F]/4.3k,40˚C[104˚F]/3.0k
Resistance 0˚C[32˚F]/15k,10˚C[50˚F]/9.6k,20˚C[68˚F]/6.3k,25˚C[77˚F]/5.4k,
30˚C[86˚F]/4.3k,40˚C[104˚F]/3.0k
TH22
Gas pipe
thermistor
FUSE 250V 6.3A
TB2 (L1,L2,G) 330V 30A
TB5
TB15
(1,2),(M1,M2,S) 330V 30A
Fuse
(Indoor con-
troller board)
Power supply
terminal bed
Transmission
terminal bed
OFF 130˚C±5˚C[266˚F±41˚F]
ON 90˚C±20˚C[194˚F±68˚F]
OFF 150˚C±5˚C[302˚F±41˚F]
ON 96˚C±15˚C[205˚F±59˚F]
Room
temperature
thermistor
Fan motor
(with Inner-
thermostat)
4-pole
Output 75W
D104P75MW
4-pole
Output 85W
D104P85MW
4-pole Output 95W
D104P95MW
4-pole
Output 140W
NC-100VM1
4-pole
Output 190W
NC-125VM1
Symbol
DC12V Stepping motor drive port dimension
3.2 (0~2000pulse) EDM-402MD
DC12V Stepping motor drive port dimension
5.2 (0~2000pulse) EDM-804MD
TH23
Inner-
thermostat
(Fan motor)
Liquid pipe
thermistor
Fan motor
capacitor
Linear
expansion valve