Mitsubishi Electronics MXZ-24UV Air Conditioner User Manual


 
30
DD
Check of LEV
No
Yes
No
Yes
Start
Turn on power supply to the outdoor unit after checking LEV coil is mounted to the
LEV body securely.
Is "click - click" sound heard?
Or, do you feel vibration of the LEV coil with a hand?
Disconnect the connector
(CN791: unit A, CN792: unit B, CN793: unit C), and
measure the resistance of LEV coil to check the
integrity.
Nomal
Replace the electronic
control P. C. board
Replace the LEV coil.
EE
Check of inverter/ compressor
No
Yes
Yes
No
0"
Infinite
Yes
No
Yes
Infinite
0"
No
Start
Disconnect the lead wire to the compressor at terminals, and turn on power supply to the indoor
and outdoor unit. Three minutes later, EMERGENCY OPERATION starts.
Is output balanced?
LED indicator the inverter
stops due to over current?
Clarify the causes by counting time until the inverter stops.
0 to 10 seconds: compressor rare short
10 to 60 seconds: compressor lock
60 seconds to 5minutes: refrigerant circuit defective
5 minutes or more: normal
Measure the voltage between
each leading to the compressor.
U (BLK) - V (WHT)
V (WHT) - W (RED)
W (RED) - U (BLK)
Output voltage
COOL: 100V(58Hz) HEAT: 100V(58Hz)
Is voltage output? W1
Turn off power supply of indoor and outdoor unit,
and measure the compressor winding resistance
between the compressor terminals.
Is there resistance of 0.27" to 0.34" between
the each terminals?
Replace the electronic
control P. C. board
with the I.P.M P. C. board.
Return the lead wire of compressor to former, and
turn on power supply to indoor and outdoor unit.
Three minutes later EMERGENCY OPERATION starts.
1. Turn off power supply of the indoor
and outdoor unit, and disconnect
the connector CN 551 in the relay
P. C. board
2. Turn on power supply to the outdoor
unit, and after 1 minutes or more
passed, check the resistance
between the connector
CN551 pin 1 and pin 2.
Check the resistance
between each terminal
After 1 minutes has passed since the
power supply of outdoor unit was
turned off, disconnect the connector
CN 553 in the noise filter P. C. board.
Check the resistance
HPS (63H2).
Replace the
relay P. C. board.
Replace the
HPS (63H2).
Replace the
compressor.
W1 • After the outdoor fan starts running, wait for 1 minutes or more before
measuring the voltage.
• The output voltage values in the above table have the tolerance of i20%.
• When cooling, heat exchanger of non-operating indoor unit frosts.
• When heating, non-operating indoor unit get warm.
(LED display:
0000
,
pp11
)
• When heating, room does not get warm.
• When cooling, room does not get cool.
(LED display:
0000
,
aa88
)
OB287--1.qxp 03.1.16 10:29 AM Page 30