Mitsubishi Electronics MUZ-GE80VAD Air Conditioner User Manual


 
66
Outline of the function
This air conditioner can memorize the abnormal condition which has occurred once.
Even though LED indication listed on the troubleshooting check table (11-3.) disappears, the memorized failure details
can be recalled.
This mode is very useful when the unit needs to be repaired for the abnormality which does not recur.
11-2. FAILURE MODE RECALL FUNCTION
1. Flow chart of failure mode recall function for the indoor/outdoor unit
NOTE: 1. Make sure to release the failure mode recall function after it is set up, otherwise the unit cannot operate properly.
2. If the abnormal condition is not deleted from the memory, the last abnormal condition is kept memorized.
Does the upper lamp of OPERATION INDICATOR lamp on the
indoor unit blink at the interval of 0.5 seconds?
Blinks: Either indoor or outdoor unit is abnormal. Beep is
emitted at the same timing as the blinking of The upper
lamp of OPERATION INDICATOR lamp. 2
Indoor unit is normal.
But the outdoor unit might be abnormal because there are
some abnormalities that can not be recalled with this way.
Con rm if outdoor unit is abnormal according to the de-
tailed outdoor unit failure mode recall function.
(Refer to 11-2.2)
No
Yes
The cause of abnormality cannot be found because the abnormality does not recur.
Setting up the failure mode recall function
Turn ON the power supply.
<Preparation of the remote controller>
While pressing both OPERATION SELECT button and TOO COOL button (MSZ-
GE25/33/35/42/50)/TEMP
button (MSZ-GE60/71/80) on the remote controller
at the same time, press RESET button.
First, release RESET button.
Hold down the other two buttons for another 3 seconds. Make sure that the indica-
tors on the LCD screen shown in the right gure are all displayed. Then release
the buttons.
Press OPERATE/STOP (ON/OFF) button of the remote controller (the set tempera-
ture is displayed) with the remote controller headed towards the indoor unit. 1
Judgment of indoor/outdoor abnormality
Before blinking, does the upper lamp of OPERATION INDICA-
TOR lamp stay ON for 3 seconds?
Stays ON for 3 seconds (without beep):
The outdoor unit is abnormal.
The indoor unit is abnormal.
Check the blinking pattern, and identify the abnormal point by referring to the
indoor unit failure mode table. (Refer to indoor unit service manual.)
Make sure to check at least two consecutive blinking cycles. 2
Releasing the failure mode recall function
Release the failure mode recall function by the following procedures.
Turn OFF the power supply and turn it ON again.
Press RESET button of the remote controller.
The outdoor unit is abnormal.
Check the blinking pattern, and identify the abnormal point by referring
to the outdoor unit failure mode table. (Refer to 11-2.3)
Make sure to check at least two consecutive blinking cycles.
3
Repair the failure parts.
Deleting the memorized abnormal condition
After repairing the unit, recall the failure mode again according to "Setting up the failure mode recall
function" mentioned above.
Press OPERATE/STOP (ON/OFF) button of the remote controller (the set temperature is displayed)
with the remote controller headed towards the indoor unit.
Press EMERGENCY OPERATION switch so that the memorized abnormal condition is deleted.
Release the failure mode recall function according to "Releasing the failure mode recall function"
mentioned above.
Operational procedure
Yes
(Blinks)
No
(OFF)
1. Regardless of normal or abnormal
condition, a short beep is emitted
once the signal is received.
2. Blinking pattern when the indoor unit is abnormal:
3.Blinking pattern when the outdoor unit is abnormal:
ON
OFF
Beeps
Repeated cycle Repeated cycle
ON
OFF
No beep Beeps
Repeated cycle
2.5-second OFF
Blinking at 0.5-
second interval
2.5-second OFF 3-second ON
Blinking at 0.5-
second interval
Beeps
Repeated cycle
2.5-second OFF
Blinking at 0.5-
second interval
No beep Beeps
Repeated cycle
2.5-second OFF
3-second ON
Blinking at 0.5-
second interval
Repeated cycle
Beeps
MSZ-GE25/33/35/42/50VA
MSZ-GE35/50VA2
MSZ-GE25/35/42/50VAD
MSZ-GE60/71/80VA
MSZ-GE80VA2
MSZ-GE60/71/80VAD
OBH532E