Mitsubishi Electronics MUZ-GE18NA Air Conditioner User Manual


 
13
ADDITIONAL REFRIGERANT CHARGE (R410A: oz.)
Refrigerant piping exceeding 25 ft. requires additional refrigerant charge according to the calculation.
Model
Outdoor unit
precharged
Refrigerant piping length (one way): ft.
25 30 40 50 60 65
MUZ-GE09NA
MUY-GE09NA
1 lb. 12 oz.
0 1.62 4.86 8.10 11.34 12.96
MUZ-GE12NA
MUY-GE12NA
2 lb. 9 oz.
MUZ-GE15NA
MUY-GE15NA
Calculation: X oz. = 1.62/5 oz. / ft. × (Refrigerant piping length (ft.) - 25)
Model
Outdoor unit
precharged
Refrigerant piping length (one way): ft.
25 30 40 50 60 70 80 90 100
MUZ-GE18NA
MUY-GE18NA
3 lb. 7 oz. 0 1.08 3.24 5.40 7.56 9.72 11.88 14.04 16.20
Calculation: X oz. = 1.08/5 oz. / ft. × (Refrigerant piping length (ft.) - 25)
NOTE: Refrigerant piping exceeding 25 ft. requires additional refrigerant charge according to the calculation.
7-1. PERFORMANCE DATA
1) COOLING CAPACITY
7 DATA
MUZ-GE09NA MUZ-GE12NA MUZ-GE15NA MUZ-GE18NA
MUY-GE09NA MUY-GE12VA MUY-GE15VA MUY-GE18VA
Model
Indoor air Outdoor intake air DB temperature (˚F)
IWB (˚F)
75 85 95 105 115
TC SHC TPC TC SHC TPC TC SHC TPC TC SHC TPC TC SHC TPC
MUZ-GE09NA
MUY-GE09NA
71 11.0 7.6 0.59 10.3 7.1 0.64 9.7 6.6 0.69 9.0 6.2 0.73 8.3 5.7 0.76
67 10.4 8.6 0.55 9.7 8.0 0.61 9.0 7.4 0.66 8.4 6.9 0.70 7.7 6.3 0.73
63 9.8 9.4 0.53 9.1 8.7 0.58 8.5 8.1 0.63 7.7 7.3 0.67 7.0 6.7 0.70
MUZ-GE12NA
MUY-GE12NA
71 14.7 8.9 0.85 13.7 8.3 0.94 12.9 7.8 1.01 12.0 7.3 1.06 11.0 6.7 1.10
67 13.9 10.3 0.81 13.0 9.6 0.89 12.0 8.9 0.96 11.2 8.3 1.02 10.3 7.6 1.07
63 13.1 11.4 0.77 12.1 10.6 0.85 11.3 9.9 0.92 10.3 9.0 0.98 9.4 8.2 1.02
MUZ-GE15NA
MUY-GE15NA
71 17.2 11.4 0.96 16.0 10.7 1.05 15.1 10.0 1.13 14.0 9.3 1.19 12.9 8.6 1.24
67 16.2 13.0 0.91 15.1 12.1 1.00 14.0 11.2 1.08 13.0 10.4 1.14 12.0 9.6 1.20
63 15.3 14.2 0.86 14.1 13.2 0.96 13.2 12.3 1.03 12.0 11.2 1.10 10.9 10.2 1.14
MUZ-GE18NA
MUY-GE18NA
71 21.1 12.2 1.46 19.7 11.4 1.60 18.5 10.7 1.72 17.2 9.9 1.81 15.8 9.1 1.89
67 20.0 14.2 1.38 18.6 13.2 1.52 17.2 12.2 1.64 16.0 11.4 1.74 14.7 10.4 1.82
63 18.7 15.8 1.31 17.4 14.7 1.45 16.2 13.6 1.57 14.7 12.4 1.67 13.4 11.3 1.74
NOTE: 1. IWB: Intake air wet-bulb temperature
TC: Total Capacity (×10
3
Btu/h)
SHC: Sensible Heat Capacity (×10
3
Btu/h)
TPC: Total Power Consumption (kW)
2. SHC is based on 80˚F of indoor Intake air DB temperature.