8
6
REFRIGERANT SYSTEM DIAGRAM
Unit: inch
MUZ-FD09NA MUZ-FD12NA
Outdoor
heat
exchanger
Flared connection
Defrost
thermistor
RT61
Discharge
temperature
thermistor
RT62
Service
port
Service
port
Flared connection
Stop valve
(with strainer)
Stop valve
(with service port)
Refrigerant flow in cooling
Compressor
4-way valve
Refrigerant flow in heating
Refrigerant pipe
ø
3/8
(with heat insulator)
Refrigerant pipe ø1/4
(with heat insulator)
R.V. coil
heating ON
cooling OFF
Strainer
#100
Capillary tube
Expansion
valve
Ambient
temperature
thermistor
RT65
Muffler
O.D. 0.118 × I.D. 0.071
× 23-5/8
(ø
3.0
× ø
1.8
×
600
)
Capillary tube
O.D. 0.118 × I.D. 0.079
× 9-7/16
(ø3.0 × ø2.0 × 240)
Outdoor heat
exchanger
temperature
thermistor
RT68
Muffler
Max. Length
A
Max. Height
difference
B
Indoor
unit
Outdoor unit
MAX. REFRIGERANT PIPING LENGTH and MAX. HEIGHT DIFFERENCE
Model
Refrigerant piping: ft. Piping size O.D: in.
Max. Length
A
Max. Height difference
B
Gas Liquid
MUZ-FD09NA
MUZ-FD12NA
65 40 3/8 1/4
ADDITIONAL REFRIGERANT CHARGE (R410A: oz.)
NOTE: Refrigerant piping exceeding 25 ft. requires additional refrigerant charge according to the calculation.
Model Outdoor unit precharged
Refrigerant piping length (one way): ft.
25 30 40 50 60 65
MUZ-FD09NA
MUZ-FD12NA
2 lb. 9 oz. 0 1.62 4.86 8.10 11.34 12.96
Calculation: X oz. = 1.62 / 5 oz. / ft. × (Refrigerant piping length (ft.) - 25)
NOTE: Refrigerant piping exceeding 25 ft. requires additional refrigerant charge according to the calculation.