Mitsubishi Electronics MUY-GE18NA Air Conditioner User Manual


 
22
MUZ-GE09NA MUZ-GE12NA MUZ-GE15NA MUZ-GE18NA
MUY-GE09NA MUY-GE12NA MUY-GE15NA MUY-GE18NA
8-2. R.V. COIL CONTROL (MUZ)
Heating
. . . . . . . . . . . . . . . . .
ON
Cooling
. . . . . . . . . . . . . . . . .
OFF
Dry
. . . . . . . . . . . . . . . . . . . .
OFF
NOTE: The 4-way valve reverses for 5 seconds right before start-up of the compressor.
ON
OFF
ON
OFF
Outdoor fan
motor
Compressor
5 seconds 15 seconds
8-1. OUTDOOR FAN MOTOR CONTROL
The fan motor turns ON/OFF, interlocking with the compressor.
[ON] The fan motor turns ON 5 seconds before the compressor starts up.
[OFF] The fan motor turns OFF 15 seconds after the compressor has stopped running.
ON
OFF
Compressor
Outdoor fan
motor
R.V.coil
ON
OFF
ON
OFF
<COOL>
5 seconds
<HEAT>
5 seconds
8-3. RELATION BETWEEN MAIN SENSOR AND ACTUATOR
Sensor Purpose
Actuator
Compressor
LEV
Outdoor fan
motor
R.V.coil
(MUZ)
Indoor fan
motor
Discharge temperature
thermistor
Protection
○○
Indoor coil temperature
thermistor
Cooling: Coil frost prevention
Heating: High pressure protec-
tion
○○
Defrost thermistor (MUZ) Heating: Defrosting
○○○○○
Fin temperature thermistor Protection
○○
Ambient temperature
thermistor
Cooling: Low ambient tempera-
ture operation
○○○
Outdoor heat exchanger tem-
perature thermistor
Cooling: Low ambient tempera-
ture operation
○○○
Cooling: High pressure protec-
tion
○○○
8
ACTUATOR CONTROL