Mitsubishi Electronics MUY-GE09NA Air Conditioner User Manual


 
21
7-5. CAPACITY AND INPUT CORRECTION BY INVERTER OUTPUT FREQUENCY
Capacity correction factors
Input correction factors
Input correction factors
Capacity correction factors
Correction of Cooling capacity
The operational frequency of compressor
Correction of Cooling total input
The operational frequency of compressor
Correction of Heating total input
The operational frequency of compressor
Correction of Heating capacity
The operational frequency of compressor
MUZ-GE09NA
MUY-GE09NA
0 50 100 150
0.5
1.0
1.5
(Hz) (Hz)
0 50 100 150
0.5
1.0
2.0
1.5
(Hz) (Hz)
MUZ-GE12NA
MUY-GE12NA
Capacity correction factors
Input correction factors
Input correction factors
Capacity correction factors
Correction of Cooling capacity
The operational frequency of compressor
Correction of Cooling total input
The operational frequency of compressor
Correction of Heating total input
The operational frequency of compressor
Correction of Heating capacity
The operational frequency of compressor
0 50 100 150
0.5
1.0
1.5
(Hz)
0 50 100 150
0.5
1.0
1.5
(Hz)
0 50 100 150
0.5
1.0
1.5
(Hz) (Hz)
MUZ-GE09NA
MUZ-GE12NA
0 50 100 150
0.5
1.0
1.5
2.0
050100150
0.5
1.0
1.5
0 50 100 150
0.5
1.0
2.0
1.5
7-6. HOW TO OPERATE FIXED-FREQUENCY OPERATION (Test run operation)
1. Press EMERGENCY OPERATION switch to start COOL or HEAT mode (COOL: Press once, HEAT: Press twice).
2. Test run operation starts and continues to operate for 30 minutes.
3. Compressor operates at rated frequency in COOL mode or 58 Hz in HEAT mode.
4. Indoor fan operates at High speed.
5. After 30 minutes, test run operation finishes and EMERGENCY OPERATION starts (operation frequency of compressor var-
ies).
6. To cancel test run operation (EMERGENCY OPERATION), press EMERGENCY OPERATION switch or any button on
remote controller.
Capacity correction factors
Input correction factors
Input correction factors
Capacity correction factors
Correction of Cooling capacity
The operational frequency of compressor
Correction of Cooling total input
The operational frequency of compressor
Correction of Heating total input
The operational frequency of compressor
Correction of Heating capacity
The operational frequency of compressor
MUZ-GE15NA
MUY-GE15NA
(Hz) (Hz)
(Hz) (Hz)
MUZ-GE18NA
MUY-GE18NA
Capacity correction factors
Input correction factors
Input correction factors
Capacity correction factors
Correction of Cooling capacity
The operational frequency of compressor
Correction of Cooling total input
The operational frequency of compressor
Correction of Heating total input
The operational frequency of compressor
Correction of Heating capacity
The operational frequency of compressor
050100150
0.5
1.0
1.5
(Hz)
050100150
0.5
1.0
1.5
(Hz)
0 50 100 150
0.5
1.0
1.5
(Hz) (Hz)
MUZ-GE15NA
MUZ-GE18NA
0 50 100 150
0.5
1.0
2.0
1.5
050100150
0.5
1.0
2.0
1.5
0 50 100 150
0.5
1.0
1.5
0 50 100 150
0.5
1.0
1.5
0 50 100 150
0.5
1.0
1.5