1. Thermostat control
Thermostat is ON or OFF by difference between room temperature and set temperature.
3-9. DRY OPERATION
3-10. HEAT OPERATION
2. High pressure protection
In HEAT operation the indoor coil thermistor detects the temperature of the indoor heat exchanger. The compressor opera-
tional frequency is controlled to prevent the condensing pressure from increasing excessively.
2. Coil frost prevention
Coil frost prevention is as same as COOL mode. (3-8.2.)
1. Thermostat control
Thermostat is ON or OFF by difference between room temperature and set temperature.
ON -1.8 °F or more
OFF less
than
-1.8 °F
-1.3 °F
Room temperature minus
set temperature (During operation)
Room temperature minus
set temperature (Initial)
Thermostat
-1.8 °F
ON less than 3.6
°F
OFF 3.6
°F or more
3 °F
3.6 °F
Thermostat
Room temperature minus
set temperature (Initial)
Room temperature minus
set temperature (During operation)