Mitsubishi Electronics MSY-ANA Air Conditioner User Manual


 
28
Correct the LEV opening according to the difference between target discharge temperature and discharge temperature.
(2) Separate correction (COOL,DRY)
(Correction by the separate super heat)
a) Correct the LEV separately by temperature difference between each gas pipe temperature and the minimum gas pipe
temperature of all.
Calculate each super heat of the unit from the expression below;
(Super heat) = (Each gas pipe temperature) - (Minimum gas pipe temperature)
Separate correction is performed according to each super heat in the table below.
MXZ-2A
Discharge temperature (°F)
LEV opening correction (pulse)
COOL HEAT
More than Target discharge temperature+18 5 8
Target discharge temperature + 18 to Target discharge temperature + 9 4 3
Target discharge temperature + 9 to Target discharge temperature + 3.6 2 1
Target discharge temperature + 3.6 to Target discharge temperature - 3.6 0 0
Target discharge temperature - 3.6 to Target discharge temperature - 9 -1 -1
Target discharge temperature - 9 to Target discharge temperature - 18 -3 -2
Target discharge temperature - 18 or less -4 -3
MXZ-3A MXZ-4A
Discharge temperature (°F)
LEV opening correction (pulse)
COOL HEAT
More than Target discharge temperature + 21.6 4 6
Target discharge temperature + 21.6 to Target discharge temperature + 9 2 2
Target discharge temperature + 9 to Target discharge temperature + 5.4 1 1
Target discharge temperature + 5.4 to Target discharge temperature - 5.4 0 0
Target discharge temperature - 5.4 to Target discharge temperature - 9 -1 -1
Target discharge temperature - 9 to Target discharge temperature - 21.6 -3 -2
Target discharge temperature - 21.6 or less -8 -8
MXZ-2A20NA
Superheat
LEV opening
correction (pulse)
more than 16.2 3
10.8 to 16.2 2
5.4 to 10.8 1
5.4 or less 0
MXZ-3A30NA
Superheat
LEV opening
correction (pulse)
more than 16.2 12
10.8 to 16.2 8
5.4 to 10.8 4
5.4 or less 0
MXZ-3A30NA-
1
MXZ-4A36NA
Operation frequency
of compressor (Hz)
Target discharge temperature (°F)
COOL HEAT
Number of operating unit
1 unit 2 units 3 units
4 units
(MXZ-4A36)
1 unit 2 unit 3 units
4 units
(MXZ-4A36)
Minimum ~ 14 95 131 134.6 140 125.6 143.6 122 122
15 ~ 23 107.6 131 134.6 140 136.4 150.8 131 122
24 ~ 32 120.2 136.4 145.4 140 149 165.2 140 122
33 ~ 41 136.4 140 149 143.6 154.4 172.4 152.6 122
42 ~ 50 149 149 158 149 154.4 172.4 161.6 131
51 ~ 59 154.4 154.4 163.4 158 154.4 172.4 168.8 140
60 ~ 68 158 158 167 158 154.4 172.4 168.8 140
69 ~ 77 167 163.4 176 161.6 154.4 172.4 168.8 140
78 ~ 86 167 167 179.6 161.6 154.4 172.4 168.8 140
87 ~ Maximum 167 176 179.6 161.6 172.4 172.4 168.8 140