Mitsubishi Electronics JY992D93901E Air Conditioner User Manual


 
F940WGOT Series (F940WGOT-TWD)
Installation Manual
JY992D93901E
This manual contains text, diagrams and explanations which will guide the reader in the correct
installation, safe use and operation of the F940WGOT-TWD-E and should be read and understood before
attempting to install or use the unit. Further information can be found in the associated manuals list below.
Specifications are subject to change without notice
Guidelines for the Safety of the User and Protection of the
F940WGOT Series.
This manual has been written to be used by trained and competent personnel. The definition of such a
person or persons is as follows:
a) Any engineer using the product associated with this manual, should be of a competent nature,
trained and qualified to the local and national standards. These engineers should be fully aware of
all aspects of safety with regards to automated equipment.
b) Any commissioning or service engineer must be of a competent nature, trained and qualified to
the local and national standards.
c) All operators of the completed equipment should be trained to use that product in a safe and
co-ordinated manner in compliance to established safety practices.
Note:
The term ‘completed equipment’ refers to a third party constructed device which contains or uses
the product associated with this manual.
Note’s on the Symbols Used in this Manual
At various times through out this manual certain symbols will be used to highlight points of information
which are intended to ensure the users personal safety and protect the integrity of equipment.
1) Indicates that the identified danger
WILL
cause physical and property damage.
2) Indicates that the identified danger could
POSSIBLY
cause physical and property
damage.
Under no circumstances will Mitsubishi Electric be liable or responsible for any consequential damage
that may arise as a result of the installation or use of this equipment.
All examples and diagrams shown in this manual are intended only as an aid to understanding the
text, not to guarantee operation. Mitsubishi Electric will accept no responsibility for actual use of the
product based on these illustrative examples.
Owing to the very great variety in possible application of this equipment, you must satisfy yourself as
to its suitability for your specific application.
Associated Manuals
Manual Name Manual Number Description
|
F940WGOT Series
(F940GOT-TWD)
Installation Manual
JY997D93901
Describes the specifications, wiring, and
installation of F940WGOT Series graphic
operation terminal. (hardware)
~
GOT-F900
OPERATION MANUAL
(describes GT Designer2)
JY997D09101
(separate volume)
Describes the operation and use of the GOT-
F900 Series graphic operation terminals and GT
Designer2.
~
GOT-F900 Series
Operation Manual
JY992D94701
(separate volume)
Describes the operation and use of the GOT-
F900 Series graphic operation terminals, GT
Designer and FX-PCS-DU/WIN-E.
~
GOT-F900 Series
Hardware Manual
(connection diagram)
JY992D94801
(separate volume)
Describes wiring and installation of the GOT-
F900 Series graphic operation terminals.
|
GT Designer2 Version1
Operating Manual
(PDF files on CD-
ROM included with
product)
Describes the operation of GT Designer2
(SW*D5C-GTD2-E) and data transfer to the
GOT-900 Series.
|
GT Designer2 Version1
Reference Manual
(PDF files on CD-
ROM included with
product)
Describes the specifications and setting of object
functions in GT Designer2 (SW*D5C-GTD2-E).
|
GT Designer
Operating Manual
Included with the
screen creation
software
Describes the operation of GT Designer
(SW*D5C-GOTR-PACKE) and data transfer to
the GOT-900 Series. (Refer to the help file)
|
FX-PCS-DU/WIN-E
SOFTWARE MANUAL
JY992D68301
(included with the
screen creation
software)
Describes the operation of FX-PCS-DU/WIN-E
screen creation software.
~
Indispensable manual
|
Either manual is necessary.
Refer if necessary, please.
Refer to the Programming manual (
ΙΙ
) or relevant hardware manuals for details concerning the applicable
PLC.
1. Introduction
The F940WGOT series (hereafter called “GOT”) is to be
mounted on the face of a control panel or operations panel, and
connected to the programming port (CPU port) or the
communication port (communication port) of a PLC.
Various devices can be monitored and PLC data changed
through the GOT screens. Several display screens are built-in to
the GOT, and additional personalized screens can be created by
the user.
1) The GOT can connect to MELSEC FX, A, QnA and Q PLCs
as well as a host of third party manufactured units. Further
information can be found in GOT-F900 Series Hardware
Manual.
2) PLC user programs can be downloaded, uploaded and monitored using programming software GX-
Developer or FX-PCS/WIN-E on a personal computer via the GOT. Further information can be found
in GOT-F900 Series Operation Manual.
3) Display screens are created using the following software:
1.1 Product Lists
Caution
During abnormal communication (including cable breakages) ages when monitor within the
GOT, communication between the GOT and programmable controller CPU is interrupted. It is
impossible to operate switches or devices in the PLC through the GOT.
Communication and normal operation resumes when the GOT system is correctly configured.
DO NOT configure emergency stop or safety features to operate through the GOT, and be
sure that there is no adverse consequences in the event of a GOT - PLC communications
malfunction.
F9GT-40FMB
User’s Manual
JY992D98601
This manual contains explanations for installation
and operating procedures of the F9GT-40FMB
data transfer adapter.
Software Name Version
GT Designer2
SW
D5C-GTD2-E
(
indicates version)
GOT-F900 and GOT-A900 Series (for Windows) screen creation software.
GT Designer
SW
D5C-GOTR-PACKE
(
indicates version)
GOT-F900 and GOT-A900 Series (for Windows) screen creation software.
SW5-F edition of SW5D5C-GOTR-PACKE (version 5.05F) or later
FX-PCS-DU/WIN-E
GOT-F900 Series (for Windows) screen creation software.
SW0PC-FXDU/WIN-E version 2.50 or later
Production Name Description
F940WGOT-TWD-E Graphic operation terminal main unit
FX-50DU-CAB0
Communication cable (GOT
CPU port in FX
0
, FX
0S
, FX
1S
, FX
0N
, FX
1N
, FX
2N
or
FX
2NC
series PLC)
The connector on the GOT side is wired straight through.
Cable length is 3m (9' 10").
FX-50DU-CAB0/EN
Communication cable (GOT
CPU port in FX
0
, FX
0S
, FX
1S
, FX
0N
, FX
1N
, FX
2N
or
FX
2NC
series PLC)
The connector on the GOT side is wired straight through. Cable length is 3m (9'
10").
FX-50DU-CAB0-**M
Communication cable (GOT
CPU port in FX
0
, FX
0S
, FX
1S
, FX
0N
, FX
1N
, FX
2N
or
FX
2NC
series PLC)
The connector on the GOT side is wired straight through.
** M is cable length. 1M: 1m (3' 3"), 10M: 10m (32' 9"), 20M: 20m (65' 7"),
30M: 30m (98' 5")
FX-40DU-CAB
Communication cable (GOT
CPU port in FX, FX
2C
, A or QnA series PLC)
The connector on the GOT side is wired straight through. Cable length is 3m (9'
10").
FX-40DU-CAB-**M
Communication cable (GOT
CPU port in FX, FX
2C
, A or QnA series PLC)
The connector on the GOT side is wired straight through.
** M is cable length. 10M: 10m (32' 9"), 20M: 20m (65' 7"), 30M: 30m (98' 5")
QC30R2
Communication cable (GOT
CPU port in Q series PLC)
The connector on the GOT side wired straight through. Cable length is 3m (9' 10").
FX-232CAB-1 Data exchange cable (GOT
Personal computer <9-pin D-sub>)
PM-20BL Battery for Alarm history, sampling and current time data retention.
F9WGT-40PSC Transparent protection sheet for F940WGOT (5 pieces)
F9GT-40FMB Data transfer adapter (Flash memory built in)
Manual Name Manual Number Description
P L C
P r o g r a m m i n g
p o r t
G O T
Note;
Do not lay signal cables near high voltage power cables or allow them to share the same
trunking duct, otherwise, effects of noise or surge induction are likely to take please. Keep
a safe distance of more than 100 mm from these wires.
Operate touch switches on the display screen by hand.
DO NOT use excessive force, or attempt operate them with hard or pointed objects.
The tip of a screw driver, pen or similar object for example may break the screen.
1.2 Dimensions and Each Part Name
Dimensions: mm (inches) MASS (Weight): 1 kg (2.2 lbs)
Accessory: Mounting brackets, Tightening bolt (M3, 6 bolts),
Packing seal for dust and water resistance
a) Display b) Mounting bracket hole
c) Communication ports
d) Mounting bracket and tightening bolt e) PM-20BL battery
f) DC power supply terminal (M3) g) Communication cable
h) Packing seal
2. Specifications
2.1 General Specifications
Port Description
COM0
RS-422 port for connecting PLC (including1:N connection) or communication
(computer link) unit <9-pin D-sub>
COM1
RS-232C port for connecting PLC (including1:N connection), printer or bar-code
reader <9-pin D-sub>
COM2
RS-232C port for connecting personal computer, printer or bar-code reader
<9-pin D-sub>
Item Specifications
Operating Temperature
Horizontal mounting: 0 ~ 50 °C (32 ~ 122 °F)
Vertical and flat mounting: 0 ~ 40 °C (32 ~ 104 °F)
Storage Temperature -20 ~ 60 °C (-4 ~ 140 °F)
Humidity 35 ~ 85% Relative Humidity, No condensation
Operating atmosphere
Must be free of lamp black, corrosive gas, flammable gas, or excessive
amount of electroconductive dust particles and must be no direct
sunlight. (Same as for saving)
Vibration Resistance
- intermittent vibration
10 ~ 57 Hz: 0.075 mm Half Amplitude
57 ~ 150 Hz: 9.8 m/s
2
Acceleration
Sweep Count for X, Y, Z: 10 times (80 min. in each direction)
Vibration Resistance
- Continuous vibration
10 ~ 57 Hz: 0.035 mm Half Amplitude
57 ~ 150 Hz: 4.9 m/s
2
Acceleration
Sweep Count for X, Y, Z: 10 times (80 min in each direction)
Shock Resistance
147m/s
2
Acceleration,
3 times in each direction X, Y, and Z
Noise Immunity 1000 Vp-p, 1micro second, 30 ~ 100 Hz, tested by noise simulator
Dielectric Withstand Voltage 500 V AC > 1 min, tested between power terminals and ground
Insulation Resistance 5 M
> at 500 V DC, tested between power terminals and ground
Ground Grounding resistance 100
or less. (Class D)
Protection IP 65F
2 1 5 ( 8 .4 6 " )
7 0 . 6
( 2 .7 8 " )
5
( 0 .2 0 " )
1 2 3 ( 4 .8 4 " )
1 3 3 ( 5 .2 4 " )
a )
b )
c )
5 0 ( 1 .9 6 " )
2 3 ( 0 .9 1 " )
2 0 5 ( 8 .0 7 " )
g )
5 ( 0 . 2 0 " ) o r le s s
7 0 . 6 (2 . 7 8 )
h )
f )
1 0 ( 0 .3 9 " )
d )
1 0 ( 0 .3 9 " )
3 4 . 5 (1 . 3 5 " )
2 3 ( 0 .9 1 " )
2 3 ( 0 .9 1 " )
3 4 . 5 (1 . 3 5 " )
e )
1 4 3 ( 5 .6 3 " )
1 3 3 ( 5 .2 4 " )
c )
24V DC