Millennium Enterprises Z33 Air Conditioner User Manual


 
882108-YIM-B-1012
30 Johnson Controls Unitary Products
TABLE 22: ELECTRICAL DATA 40 TON W/ELECTRIC HEAT R-410A
Voltage
Compressors
(each)
OD Fan
Motors
(each)
Supply Blower
Motor
Electric Heat Option
MCA
1
(Amps)
Max Fuse
2
/
Breaker
3
Size
(Amps)
Qty RLA LRA MCC FLA HP FLA Option KW Applied Stages Amps
208-3-60 4 30.1 255 47 5.8
10 30.8
E4 40 30 1 83
182 200
15 46.2 201 225
20 59.4 218 250
25 74.8 237 300
10 30.8
E8 80 60 2 167
205 225
15 46.2 225 250
20 59.4 241 300
25 74.8 260 300
230-3-60 4 30.1 255 47 5.8
10 28
E4 40 36.8 1 92
179 200
15 42 196 225
20 54 211 250
25 68 229 250
10 28
E8 80 73.6 2 184
220 250
15 42 237 250
20 54 252 300
25 68 270 300
460-3-60 4 16.7 114 26 2.9
10 14
E4 40 36.8 1 46
97 110
15 21 105 125
20 27 112 125
25 34 121 150
10 14
E8 80 73.6 2 92
110 125
15 21 119 125
20 27 126 150
25 34 135 150
10 14
E1 108 99.4 3 125
142 175
15 21 151 175
20 27 158 175
25 34 167 200
575-3-60 4 12.2 80 19 2.2
10 11
E4 40 36.8 1 40
72 80
15 17 79 90
20 22 85 100
25 27 91 110
10 11
E8 80 73.6 2 80
94 110
15 17 102 110
20 22 108 125
25 27 114 125
10 11
E1 108 99.4 3 108
122 150
15 17 130 150
20 22 136 150
25 27 142 150
1.
Minimum Circuit Ampacity.
2.
Dual Element, Time Delay Type.
3.
HACR type per NEC.