Maxon Telecom 300 Burner User Manual


 
Low temperature burners - INDITHERM
®
www.maxoncorp.com
combustion systems for industry
MAXON reserves the right to alter specifications and data without prior notice.
© 2008 Copyright Maxon Corporation. All rights reserved.
1-2.3-17
E-m-7/08
Installation and operation instructions for INDITHERM
®
burners
Application requirements
Supporting burner air and gas piping
The INDITHERM
®
burner shall not be used as support for the piping to the burner. Gas and air piping shall be supported in such a
way that no additional loads will be created on the burner.
Burner mounting flange loads
Check burner weight and reinforce burner mounting flange or combustion chamber/furnace back wall if necessary to support the
complete burner weight.
Installation instructions
Storage of INDITHERM
®
burners
INDITHERM
®
burners shall be stored dry (inside). Burner blocks have been cured carefully before shipment and shall be kept dry.
Wetting of the blocks could result in premature failures.
Handling of INDITHERM
®
burners
INDITHERM
®
burners are shipped as complete units. Handle burners with care, using proper equipment during unpacking,
transport, lifting and installation. Any impact on the burner could result in damage. To prevent damage in transit, accessories such
as flame rods, control valves, UV-scanners, may be packed separately and shipped loose.
Orientation of INDITHERM
®
burners
INDITHERM
®
burners can be mounted and fired in any direction. However we advise to avoid orientations which can permit flame
supervision ports to collect debris and/or moisture. Also check limitations on orientation of other components mounted on the
burner head.
Burner mounting
Bolt the burner to the installation’s burner mounting flange. Use proper gaskets between burner and burner mounting flange
(option available).Tighten the flange bolting with correct torque. Retighten all bolts after first firing and regularly after
commissioning.