SAFETY
INFORMATION
Continued
WARNINGS
(Continued)
• Use only kerosene or No. 1 fuel oil to avoid risk of fire or explosion. Never use
gasoline, naphtha, paint thinners, alcohol, or other highly flammable fuels.
• Fueling
a) Personnel involved with fueling shall be qualified and thoroughly familiar with
the manufacturer's instructions and applicable regulations regarding the safe fu-
eling of heating units.
b) Only the type of fuel specified on the heater's data plate shall be used.
c) All flame, including the pilot light, if any, shall be extinguished and the heater
allowed to cool, prior to fueling.
d) During fueling, all fuel lines and fuel-line connections shall be inspected for leaks.
Any leaks shall be repaired prior to returning the heater to service.
e) At no time shall more than one day's supply of heater fuel be stored inside a
building in the vicinity of the heater. Bulk fuel storage shall be outside the struc-
ture.
f) All fuel storage shall be located a minimum of 762cm (25 feet) from heaters,
torches, welding equipment, and similar sources of ignition (exception: the fuel
reservoir integral with the heater unit).
g) Whenever possible, fuel storage shall be confined to areas where floor penetra-
tions do not permit fuel to drip onto or be ignited by a fire at lower elevation.
h) Fuel storage shall be in accordance with the authority having jurisdiction.
• Never use heater where gasoline, paint thinner, or other highly flammable vapors are
present.
• Follow all local ordinances and codes when using heater.
• Heaters used in the vicinity of tarpaulins, canvas, or similar enclosure materials
shall be located a safe distance from such materials. The recommended mini-
mum safe distance is 304.8cm (10 feet). It is further recommended that these
enclosure materials be of a fire retardant nature. These enclosure materials shall
be securely fastened to prevent them from igniting or from upsetting the heater
due to wind action.
• Use only in well-vented areas. Before using heater, provide at least a
2800 square cm
(three-square-foot) opening of fresh, outside air for each 100,000 Btu/Hr of rating.
• Use only in places free of flammable vapors or high dust content.
• Use only the electrical voltage and frequency specified on model plate.
• Use only a three-prong, grounded extension cord.
• Minimum heater clearances from combustibles:
Outlet: 250 cm (8 Ft.) Sides, Top, and Rear: 125 cm (4 Ft.)
• Locate heater on a stable and level surface if heater is hot or running or a fire may
occur.
• When moving or storing heater, keep heater in a level position or fuel spillage may
occur.
• Keep children and animals away from heater.
• Unplug heater when not in use.
• Heater is equipped with a thermostat and may start anytime.
• Never use heater in living or sleeping areas.
• Never block air inlet (rear) or air outlet (front) of heater.
• Never move, handle, refuel, or service a hot, operating, or plugged-in heater.
• Never attach duct work to front or rear of heater. Using duct work could reduce the
necessary air flow of the heater. Heater would produce excessive carbon monoxide.