Majestic Appliances SC42A Indoor Fireplace User Manual


 
16
SR/SC Series "A" Woodburning Fireplace
7412948
Hearth Installation
A hearth extension is required to protect a combustible
floor in front of the fireplace. Refer to Figure 23 for
minimum dimensions and mounting detail.
NOTE: Hearth Extension must not cover the air
inlet opening of a fireplace.
The hearth extension described in Figure 23 must be a
durable noncombustible material with a minimum
(total) Rt value of 1.09; refer to Figure 24 for ex-
amples. The overall height (above a combustible
floor), depth and width must be as indicated, with the
extension centered to the fireplace opening.
The top of insulation must be covered with a noncom-
bustible decorative covering or a piece of .018”
minimum sheet metal, to protect hearth extension
material. (Fig. 23)
Secure the hearth extension to the floor to prevent
shifting, using trim molding or other similar means at
three (3) outer edges. Seal crack between the fire-
place hearth and hearth extension with a noncombus-
tible material. (Figs. 23 and 25)
FP594
Fig. 23 Combustible side wall protection and hearth extension dimensions.
Minimum Wall Clearances
WITH
Noncombustible
Surround Facing
WITHOUT
Noncombustible
Surround Facing
Minimum Hearth Extension Dimensions
(for On-Site Construction)
G
H
G
J
Seal cracks
between the
fireplace
and hearth
extension with
noncombustible
material
Safety strips
must overlap
¹⁄₂" minimum
May install
noncombustible
decorative
covering
OR .018" min.
sheet metal
FIREPLACE
HEARTH
COMBUSTIBLE
FLOOR
MINIMUM
INSULATION
VALUE "R"
4" MIN.
FIREBOX
OPENING
A - Min. clearance
to combustible
perpendicular wall
B - Min. clearance
to combustible
perpendicular wall when
using noncombustible wall shield*
SIDE
WALL
SIDE
WALL
F**
C**
E
E
D
4" BRICK
(Example material)
Combustible material permitted within shaded area.
*
Noncombustible wall shield requires 1" CFM Corporation
EH2416 insulation (minimum R Value = 1.85) between
decorative noncombustible rigid covering and combustible wall.
Minimum height and width is 40" x 40".
**
Dimension/degree of angle will vary depending on thickness
of noncombustible surround facing.
4"
Shaded area starts
1/2" away from
edge of unit.
ABCDE F G HJ
SR/SC36A 16" 12" 48° 41° 18" 14" 7³⁄₄" 16" 48"
406mm 305mm 457mm 356mm 197mm 406mm 1219mm
SR/SC42A 20" 12" 42° 35° 18" 14" 11¹⁄₂" 20" 61¹⁄₂"
508mm 305mm 457mm 356mm 292mm 508mm 1562mm
Side Wall Protection
Adjacent combustible side walls that are within the
minimum dimensions shown in Figure 23 of fireplace
opening must be protected with CFM Corporation Wall
Shield Model SP40 or a specifically built wall shield
described below.
The special wall shield design described in Figure 20
is an alternate method of adding protection to side
walls and can be used in place of the SP40 with the
same wall clearances specified for the SP40. Rt must
=1.85 minimum.
Examples of wall shield insulation:
1. Manville - CERAFORM 126, K=.27,
1/2 inches thick
2. CFM Corporation - EH2416, K = .458,
1 inch thick required.