System design
The Extinguishing Control Panel LC216-1 can be used
to realize an extinguishing system with one fl ooding
zone according to EN 12094-1. In an extinguishing
system that does not require a design according to
EN 12094-1, up to 8 fl ooding zones can be actuated.
The function of the Extinguishing Control Panel LC216-1
is integrated into the Fire Detection Control Panels
BC216-1 and BC216-1CE and can be enabled by means
of an options circuit.
In the networked Extinguishing Control Panel LCnet216,
up to 127 extinguishing systems with a total of 127
fl ooding zones can be implemented. Each extinguishing
system can control up to 32 fl ooding zones, and each
LCnet sectional control panel can administrate up to 8
fl ooding zones.
The Extinguishing Control Panel LCnet216 can be imp-
lemented with all types of Fire Detection Control Panels
Series BC216 that are suitable for networking.
These are
the BCnet sectional control panel with operating
unit BC216-2 and without operating unit BC216-3
in a wall-mount cabinet,
the BCnet Sectional Control Panel Extension
BCE216-3LG for installation into a BCnet Sectional
Control Panel BC216-2 or BC216-3,
the fi re detection control panel with operating unit
BC216-1CE with installed Network Interface Modu-
le NIF5-1M, and the BCnet sectional control panel
without operating unit BC216-3CE, for installation
into a 19“ housing, as well as
the Fire Detection Control Panel Modules
BCM216-3EPS, BCM216-3E and BCM216-3ELG
for sliding into a 19“ rack.
A redundant design of the extinguishing control panel
according to EN 12094-1 can be implemented by
means of the fi re detection control panel modules in
19“ slide-in technology.
Other versions of the Fire Detection Control Panel Series
BC216 can be implemented according to EN 12094-1
without redundancy – with one fl ooding zone per
BCnet sectional control panel.