LST EN 12094-1 Smoke Alarm User Manual


 
© LABOR STRAUSS SICHERUNGSANLAGENBAU GMBH • A-1231 WIEN • WIEGELESTRASSE 36 • TEL +43 1 52114-0 • FAX +43 1 52114-27
OFFICE@LST.AT • WWW.LST.AT • ALL RIGHTS RESERVED
BC216-2_DBL_LST_EN_0804.PDF • PAGE 2
ABuilding Safety. Building Security.
Clear Concept
The BCnet sectional control panels BC216-2 and
BC216-3 are modularly designed sectional control pa-
nels of the fi re detection control panel BCnet216 that
are connected via the Global Security System network
GSSnet. Depending on their confi guration, they provide
the following features:
• The Conventional Detector Interface GIF8-1 permits
the connection of automatic detectors and manual
call points in conventional technology as well as spe-
cial detectors with contact output. Individual detector
identifi cation can be achieved by means of an optio-
nal address module.
• Detectors and modules in ADM loop technology can
be connected to the Loop Interface LIF64-1. Depen-
ding on the parameterisation, either the Apollo/Disco-
very protocol or the System Sensor/200 protocol is
used to achieve bi-directional data transfer.
• Since the BCnet216 is compatible to LST fi re detec-
tion control panels of previous generations, the ex-
change or expansion of existing systems in conventi-
onal technology or ADM loop technology is possible.
The existing detector installation can be used without
changes.
• The optional Fire Brigade Interface FWI2-1 serves
for the connection of two independent transmitting
devices for a direct interconnection to a designated
alarm respondent (e.g., the fi re brigade) as well as
for the connection of a country-specifi c fi re brigade
control unit. By using the Fire Brigade Interface Addi-
tional Board FWZ2-1, a line supervision for both of the
transmitting devices is accomplished.
• Customizable outputs and logical combinations of
detectors and detector zones for the activation of
external controls and alarming devices facilitate ma-
ximum fl exibility. Thus, no additional expenses arise
for external relays, logic gates or timers. Thanks to
the wide range of parameterisation possibilities, indi-
vidual requirements even under the most diffi cult am-
bient conditions can be combined into a reasonable
fi re protection strategy.
• By integrating input and output modules on any positi-
on in the loop you can realize enablements or disable-
ments as well as control tasks in your system without
having to care for additional wires.
• The free combination of detectors and modules into
logic sectors allows for the joint operation of defi ned
parts of the system even beyond the limits of loops
or sectional control panels.
• The use of unshielded loop cables allows for cost-
saving and uncomplicated installation as well as for
the possibility of reusing the existing cabling.
• An event memory allows for the display of the la-
test 500 events on the main operating unit of the
BCnet216 at any time. Thus, all system conditions
and user operations that occurred are documented
with all the necessary information in a clearly laid out
way.
• At a central processing board failure, the diversifi ed
redundancy concept ensures secure alarm recogniti-
on.
• The processor-monitored power supply ensures per-
manent surveillance and charging of the batteries.
This way, even during a mains power failure the un-
troubled and uninterrupted operation (for more than
72 hours depending on the design) is guaranteed.
• Three hierarchized authorization levels for operation
and parameterisation facilitate a high degree of secu-
rity against unauthorized access.
• On a sectional control panel with display and operating
fi eld (BC216-2), depending on the parameterisation,
the entire system or only specifi c sectional control
panels can be operated. In the same way, the display
of events from the other sectional control panels can
be suppressed.
• The parameter data can be created by means of the
PC software PARSOFT and loaded into the control pa-
nel in a comfortable way. Thus, a quick and effi cient
transfer of the system confi guration into the control
panel is guaranteed.
• AUTO setup facilitates parameterisation when the
control panel is commissioned or expanded and thus
helps to save time.
The fl at wall mount cabinet allows for an easy mounting
in virtually any place of the building. Thanks to its mo-
dern, ageless design, architectural requirements and
demands of the respective regulations are ideally com-
bined. The compact design allows for the accommoda-
tion of the function modules, the auxiliary modules and
batteries up to 22Ah apart from the central processing
board in the standard case. If a higher battery capacity
is needed, an auxiliary case of the same design is avai-
lable. BCnet216 thus stands for modularity and easy
expansion.
These products comply with all relevant standards of
EN 54 and are VdS-certifi ed. In addition, the products
also hold several country-specifi c approvals and certi-
fi cates. LST‘s high quality level is secured by a perma-
nently monitored quality management system certifi ed
by ISO 9001.