LST BC06-2EXT Home Security System User Manual


 
© LABOR STRAUSS SICHERUNGSANLAGENBAU GMBH • A-1231 WIEN • WIEGELESTRASSE 36 • TEL +43 1 52114-0 • FAX +43 1 52114-27
OFFICE@LST.AT • WWW.LST.AT • ALL RIGHTS RESERVED
BC06EXT_DBL_LST_EN_0826.PDF • PAGE 4
ABuilding Safety. Building Security.
Specifi cations
Mains voltage 230VAC +10/-20%, 47...63Hz
Output/nominal voltage typ. 27.6VDC
Output current max. 2.2A
Output current siren outputs
output 1 max. 1A
output 2 max. 0.5A
(the sum of the currents of the signalling devices that are connected to the two outputs must not exceed 1A!)
Output current, extinguishing output max. 1A
Output current, activated condition output/signal output max. 500mA per output
Own current consumption (incl. extinguishing board) at 24V typ. 80mA (without optional componentries, line termination 5.6k
Ω)
typ. 65mA (without optional componentries, line termination 47µF)
Line voltage typ. 20V (line termination 5.6k
Ω)
typ. 23V (line termination 47µF)
Line current without fi re detectors typ. 3.7mA (line termination 5.6k
Ω)
typ. 0mA (line termination 47µF)
Line termination 5.6k
Ω or 47µF
Line resistance max. 50
Ω per core
Ambient temperature -5°C to +50°C
Relative humidity max. 95% (no condensation)
Dimensions W × H × D 330 × 330 × 90 (mm)
Colour grey-white, RAL 9002
Weight without batteries approx. 3kg
Approvals 0786-CPD-20300
VdS pending
Fire Detection Control Panel BC06-1EXT
Order number 210223
Order name Fire Detection Control Panel BC06-1EXT/INT1
Fire Detection Control Panel BC06-2EXT
Order number 210224
Order name Fire Detection Control Panel BC06-2EXT/INT1
Functions of EN 12094-1
All mandatory functions of EN 12094-1 are integrated
into the Fire/Extinguishing Control Panels BC06-1EXT
and BC06-2EXT. Furthermore, the most important opti-
onal functions of this standard are supported:
Parameterisable pre-discharge-warning time for the
delay of the activation
Detector zone „extinguishing medium active“ se-
lectable for detecting the fl ow of the extinguishing
medium
Monitoring of components of the extinguishing sys-
tem
• Input for connection of an emergency hold device
• Monitoring of a disable device
• Parameterisable fl ooding time
Possibility to switch to the „manual only mode“
Transmission of the triggering signal to further actu-
ations within the extinguishing system – for example,
warning devices
Transmission of the triggering signal to further actua-
tions outside the extinguishing system – for example,
for turning off the air conditioning system
• Emergency abort device can be connected
Activation of alarming devices with different alarm
signals