By means of the Extinguishing Board EXB1-1, the
Fire/Extinguishing Control Panels BC06-1EXT and
BC06-2EXT provide numerous inputs and outputs with
xed or parameterisable function. With that, the follo-
wing components of an extinguishing system can be ac-
tuated and monitored in accordance with EN 12094-1:
Activation devices for the manual activation of the
ooding process
Emergency hold devices for the manual delay of the
ooding process
Emergency abort devices for aborting the fl ooding
process
Fault detection devices for monitoring the compon-
ents of the extinguishing system
A disable device for the indication of the mechanical
blocking of the extinguishing agent‘s network
A fl ooding switch that indicates the fl ow of the extin-
guishing agent
A device for switching to the manual mode – for ex-
ample, a key switch
Signalling devices for indicating the activated conditi-
on and the released condition
The control device for activating the ooding – for
example, a solenoid valve
Auxiliary outputs for actuating fl aps or for turning off
devices and systems
Extinguishing control
The operating fi eld of the Fire/Extinguishing Control Pa-
nels BC06-1EXT and BC06-2EXT provides 13 LEDs for
displaying the operating conditions and 4 buttons for
the operation of the extinguishing system.
The LEDs indicate the following operating conditions:
• Pre-activation/activation of the extinguishing module
• Released condition of the extinguishing output
• Extinguishing output fault
• Extinguishing module fault/disablement
Extinguishing medium fault/fault of the fault input
• Emergency hold/emergency hold device fault
• Activation device fault/disablement
• Signal output activated/signal output faulty/disabled
• Manual mode of the extinguishing module
• Fault of the activated condition output
The buttons on the operating fi eld have the following
functions:
• Disable/enable the extinguishing module
• Start/terminate the manual mode
• Disable/enable the activation devices
• Disable/enable the signal output