© LABOR STRAUSS SICHERUNGSANLAGENBAU GMBH • A-1231 WIEN • WIEGELESTRASSE 36 • TEL +43 1 52114-0 • FAX +43 1 52114-27
OFFICE@LST.AT • WWW.LST.AT • ALL RIGHTS RESERVED
5251EM_DBL_LST_EN_0804.PDF • PAGE 2
ABuilding Safety. Building Security.
Specifi cations
Operating voltage Supply through loop voltage
Current consumption max. 200µA (quiescent)
Alarm temperature
Class A1S typ. 58°C (maximum principle), max. room height 7.5m
Class A1R typ. 58°C (rate-of-rise principle), max. room height 7.5m
Class BS typ. 78°C (maximum principle), max. room height 6m
Operating temperature
Classes A1S and A1R max. +45°C
Class BS max. +68°C
Ambient temperature -20°C to +60°C (continuous operation)
Relative humidity 10 – 93% (no condensation)
Dimensions ø × H 102 × 51 (mm)
Colour cream
Weight 102g
Approval VdS G200094
Order number 242002
Order name Thermal Detector/Anal./200/SS 5251EM