Lochinvar E B N 150 Boiler User Manual


 
Available Firing Systems
M9 Hot Surface Ignition with
Electronic Supervision
(Standard)
M7 California Code
Efficiency+
®
Boiler Dimensions & Specifications
Lochinvar Corporation • 300 Maddox Simpson Pkwy • Lebanon, TN 37090 • 615-889-8900 / Fax: 615-547-1000
www.Lochinvar.com
FG-5M-3/10-Printed In U.S.A.
EBN-04 Revised EBN-04 9/08)
For Ease In Ordering
By Model Number
E B N 150
This is a 150,000 Btu/hr
natural gas Efficiency
+
boiler.
Efficiency+
Boiler
Natural Gas
Input
Standard Features
84% AFUE
Two Stage Firing
Sealed Combustion Chamber
Stainless Steel Burners
Low NOx Operation Exceeds the most
Stringent Air Quality Requirements
ASME Copper Finned Tube Heat Exchanger
160 PSI Working Pressure
Gasketless Heat Exchanger Design
Automatic Reset High Limit
Loch-Heat Ceramic Tile Combustion Chamber
Hot Surface Ignition
ASME Pressure Relief Valve
24 Volt Control System
Pump Relay
10 Year Limited Warranty
on Heat Exchanger
(See warranty for details)
Optional Equipment
Adjustable High Limit
w/ Manual Reset
Alarm Bell
Cupro-Nickel Heat Exchanger
Flow Switch
Indoor/Outdoor Reset
Manual Reset Low Water Cut-Off
w/test
MP
2
Sequencer
Stack Frame
Pump Delay w/ Freeze Protection
Registered Under U.S. Patent #5,989,020
Venting Options
Conventional
Vents into conventional flue or
vent breaching using Type B
double wall vent.
** E+ DirectAire Vent with
Sidewall Inlet
Draws fresh combustion air from
an outside wall horizontally, and
vents combustion by-products
through a vertical flue.
Direct Vent Vertical
Draws fresh combustion
air from outside, and vents
combustion by-products
through a vertical flue.
** Direct Vent Horizontal
Draws fresh combustion air
from outside, then vents
by-products through a side wall.
** Outdoor Vent Kit
Use when indoor space is a
problem or if outdoor location
gives better access.
** Requires factory supplied vent kit.
Efficiency+ Boiler Dimensions & Spec i fi ca tions
Input Heating Net
Model Max AFUE Capacity I=B=R Gas Vent Shipping
Number MBH % MBH MBH B D E G Conn. Size Weight
EBN150 150 83.2 129 112 19-3/4” 16” 7-1/4” 11-3/4” 3/4” 5” 245
EBN200 200 83.1 170 148 23-3/4” 20” 9-1/4” 11-3/4” 3/4” 5” 265
EBN250 250 83.2 218 190 27-1/2” 23-3/4” 11” 11-3/4” 3/4” 6” 290
EBN300 300 84.0 252 219 31-1/4” 27-1/2” 13” 11-3/4” 3/4” 6” 310
Notes: Change ‘N’ to ‘L’ to denote L.P. gas models Electrical Requirements: 120 VAC / 2 AMP Water connections are 1-1/2” NPT
Net ratings based on piping and pick-up allowance of 1.15 Performance data based on manufacturer test results.