Job Information Type:
Ordering Information
Explanation of Catalog Number. Example: H9S2GLR224120PGGLR
Options/Accessories
Fusing: Internal fast blow fusing: SUFFIX: GLR.
Internal slow blow fusing: SUFFIX: GMF.
Drywall Kit: Order Catalog Number: FK92X2 .
Electrical Wiring Options: Consult factory.
For motion or light sensor. See Folio OA20-10..
Specifications
Performance: In an installation of 2 lamp 14W luminaires in a room cavity
ratio of 1, with reflectance 80% ceiling, 50% wall, 20% floor, the C.U. shall not
be less than .80. To reduce glare the average brightness at 65° shall not exceed
1954 candelas per square meter. To control veiling reflections, luminaire output
in the 30°-90° zone shall not be less than 73.1%.
Materials: Chassis parts are die-formed code gauge steel.
Lamp Shield: Linear prismatic translucent DR acrylic lens.
Finish: Chassis exterior – baked white acrylic enamel. Cavity – baked flat
white acrylic enamel. Phosphate undercoating. Reflector – low iridescence
specular aluminum .95% reflectance.
Specifications (continued)
Electrical: Thermally protected class “P’ ballast C.B.M. approved, non PCB. If
K.O. is within 3" of ballast, use wire suitable for at least 90°.
UL Listed for damp locations.
Labels: I.B.E.W./UL and ULc Listed.
This product may have a mercury containing lamp. Manage in accord with
Disposal Laws. See: www.lamprecycle.org
Options:
Add appropriate
suffix to catalog
no., ie: (GLR)
HP90
Direct/Indirect
Recessed
S
Body Style:
S = Static
2
Fixture
Width
G
Ceiling Type:
Fits both
Standard Grid
and
Slot Grid
L
Acrylic Lens Lamp:
(By Others)
14=T5 14W
24=T5HO 24W
(Nominal 24")
R
Reflector:
Specular
Aluminum
2
Lamp
Quantity
2=2 Lamp
Ballast Type:
<20THD <10THD
2 Lamp Elec. T5 PG ††
(14 Watt)
2 Lamp Elec. T5HO PG ††
(24 Watt)
††Program Rapid Start (UNV only)
0.0 45.0 90.0 FLUX
0 602 602 602
5 599 604 609 58
15 577 613 642 173
25 535 612 633 275
35 474 548 562 336
45 393 448 456 339
55 292 329 355 295
65 184 231 277 231
75 89 145 178 145
85 17 23 19 29
90 222
Model No. H9S2GLR214120PG
LER = FP - 58.9 IW - 31.9 BF - 1.0
Comparative yearly lighting energy cost per
1000 lumens = $4.07
Report Number: G2006122
Catalog Number: H9S2GLR214120PG
Lamps: F14T5
Luminaire: HP90 2' x 2' with linear
prismatic lens.
Ballast: B228PUNV-C
Report is based on 1220 Lumens per lamp.
Efficiency: 77.1%
CIE Type-Direct-Indirect
Plane: 0-Deg 90-Deg
Spacing Criteria: 1.3 1.4
Shielding Angles: 90 90
Plane: 0-Deg 90-Deg
Luminous Length: 22.800 22.800
CANDELA DISTRIBUTION
0
AVERAGE AVERAGE AVERAGE AVERAGE
IN DEG. 0-DEG. 45-DEG. 90-DEG.
45 1657. 1888. 1922.
55 1517. 1710. 1845.
65 1298. 1629. 1954.
75 1025. 1670. 2050.
85 581. 787. 650.
LUMINANCE DATA IN CANDELA/SQ. METER
COEFFICIENTS OF UTILIZATION –
ZONAL CAVITY METHOD. EFFECTIVE
FLOOR CAVITY REFLECTANCE 0.20
0
RC 80 50 30
RW 70 50 30 50 30 10 50 30 10
01848077757370727068
02767064656158635956
03696155585248555147
04635447514641494441
05584841464035443935
06544336413531403531
07503933373227363127
08463629342924332824
09433326322622312622
10 41 30 24 29 24 20 28 23 20
ZONE LUMENS % LAMP % FIXT
00-030 506 20.7 26.9
00-040 842 34.5 44.7
00-060 1476 60.5 78.5
00-090 1881 77.1 100.0
90-180 0000 0.0 000.0
00-180 1881 77.1 100.0
ZONAL LUMEN SUMMARY
Model No. HP9S2GLR224120PG
LER = FP - 66.5 IW - 47.0 BF - 1.0
Comparative yearly lighting energy cost per
1000 lumens = $3.61
Report Number: G2006116
Catalog Number: HP9S2GLR224120PG
Lamps: F24T5 HO
Luminaire: HP90 2' x 2' with linear
prismatic lens.
Ballast: B224PUNV-C
Report is based on 2000 Lumens per lamp.
Efficiency: 76.5%
CIE Type-Direct-Indirect
Plane: 0-Deg 90-Deg
Spacing Criteria: 1.3 1.4
Shielding Angles: 90 90
Plane: 0-Deg 90-Deg
Luminous Length: 22.800 22.800
0.0 45.0 90.0 FLUX
0 955 955 955
5 953 958 966 92
15 934 976 1019 277
25 886 980 1008 443
35 786 878 895 539
45 648 720 728 546
55 485 534 569 479
65 324 381 446 382
75 177 244 291 248
85 34 43 35 53
90 333
CANDELA DISTRIBUTION
0
AVERAGE AVERAGE AVERAGE AVERAGE
IN DEG. 0-DEG. 45-DEG. 90-DEG.
45 2731. 3035. 3069.
55 2520. 2775. 2957.
65 2285. 2687. 3146.
75 2038. 2810. 3351.
85 1163. 1471. 1197.
LUMINANCE DATA IN CANDELA/SQ. METER
COEFFICIENTS OF UTILIZATION –
ZONAL CAVITY METHOD. EFFECTIVE
FLOOR CAVITY REFLECTANCE 0.20
0
RC 80 50 30
RW 70 50 30 50 30 10 50 30 10
01837976747269716967
02756964656157625956
03696054575248555047
04635346504540494440
05584841453935443834
06534336413530393430
07493932373127363127
08463529342824332824
09433226312522302521
10 40 30 24 29 23 20 28 23 19
ZONE LUMENS % LAMP % FIXT
00-030 811 20.3 26.5
00-040 1350 33.8 44.1
00-060 2376 59.4 77.7
00-090 3060 76.5 100.0
90-180 0000 00.0 000.0
00-180 3060 76.5 100.0
ZONAL LUMEN SUMMARY
Lightolier a Genlyte company www.lightolier.com
Technical Information: (978) 657-7600 • Fax (978) 658-0595
631 Airport Road, Fall River, MA 02720 • (508) 679-8131 • Fax (508) 674-4710
We reserve the right to change details of design, materials and finish.
© 2006 a Genlyte company
Section 5/Folio M32-15
Voltage:
120, 277 or
UNV=120-277
H9
Standard HP90
HY
For NYC Code – I.B.E.W. Manufactured
HN